Commissioning
EL37x2
154
Version: 3.5
6.6.4
Single-ended/differential typification
For analog inputs Beckhoff makes a basic distinction between two types:
single-ended
(SE) and
differential
(DIFF)
, referring to the difference in electrical connection with regard to the potential difference.
The diagram shows two-channel versions of an SE module and a DIFF module as examples for all multi-
channel versions.
Fig. 196: SE and DIFF module as 2-channel version
Note: Dashed lines indicate that the respective connection may not necessarily be present in each SE or
DIFF module. Electrical isolated channels are operating as differential type in general, hence there is no
direct relation (voltaic) to ground within the module established at all. Indeed, specified information to
recommended and maximum voltage levels have to be taken into account.
The basic rule:
• Analog measurements always take the form of voltage measurements between two potential points.
For voltage measurements a large R is used, in order to ensure a high impedance. For current
measurements a small R is used as shunt. If the purpose is resistance measurement, corresponding
considerations are applied.
◦ Beckhoff generally refers to these two points as input+/signal potential and input-/reference
potential.
◦ For measurements between two potential points two potentials have to be supplied.
◦ Regarding the terms "single-wire connection" or "three-wire connection", please note the
following for pure analog measurements: three- or four-wire connections can be used for
sensor supply, but are not involved in the actual analog measurement, which always takes
place between two potentials/wires.
In particular this also applies to SE, even though the term suggest that only one wire is
required.
• The term "electrical isolation" should be clarified in advance.
Beckhoff IO modules feature 1..8 or more analog channels; with regard to the channel connection a
distinction is made in terms of:
◦ how the channels WITHIN a module relate to each other, or
◦ how the channels of SEVERAL modules relate to each other.
The property of electrical isolation indicates whether the channels are directly connected to each
other.
Summary of Contents for EL3702
Page 2: ......
Page 6: ...Table of contents EL37x2 6 Version 3 5...
Page 83: ...Commissioning EL37x2 83 Version 3 5 Fig 92 Incorrect driver settings for the Ethernet port...
Page 142: ...Commissioning EL37x2 142 Version 3 5 Fig 184 Process data tab SM0 EL37x2...
Page 143: ...Commissioning EL37x2 143 Version 3 5 Fig 185 Process data tab SM1 EL37x2...