Commissioning
EL37x2
145
Version: 3.5
SM1, PDO Assignment 0x1C11
Index
Index of excluded
PDOs
Size (byte.bit)
Name
PDO content
0x1B01
-
2.0
Ch 2
CycleCount
Index 0x6800:01 -
Ch 2 CycleCount
0x1A80
..
0x1AE3
-
2.0
Ch 2 Sample 0
..
Ch 2 Sample 99
Index 0x6000:01 -
Ch 2 Value
..
Index 0x6630:01 -
Ch 2 Value
SM2, PDO assignment 0x1C12
Index
Index of excluded
PDOs
Size (byte.bit)
Name
PDO content
0x1B10
-
4.0
Ch 2
CycleCount
Index
0x1D09:98:01 -
StartNextTimeLatc
h
Table 2: PDO assignment of sync managers
6.5.3
Oversampling settings, distributed clocks (DC)
Sample: Setting 2-channel, 2 times oversampling
The oversampling factor can be set in the “DC” tab (see Fig.
Process data tab, sample setting 2-channel, 2
times oversampling
). If only one channel of the EL37x2 is required, the corresponding operating mode can
be selected as shown in Fig.
Process data tab, example setting two-channel, 2 x oversampling
, in order to
reduce the process data. When an entry is selected in the dialog, the correct sampling ratio at distributed
clock level and the correct number of process data to be transferred are set automatically.
Note
Sampling frequency
If an oversampling factor is required that does not appear in the list, the user has to specify
the ratio between the SYNC0 pulse and the SYNC1 pulse within the permitted limits, based
on the information found in "Basic Function Principles". See the
example [
}
151]
.
Summary of Contents for EL3702
Page 2: ......
Page 6: ...Table of contents EL37x2 6 Version 3 5...
Page 83: ...Commissioning EL37x2 83 Version 3 5 Fig 92 Incorrect driver settings for the Ethernet port...
Page 142: ...Commissioning EL37x2 142 Version 3 5 Fig 184 Process data tab SM0 EL37x2...
Page 143: ...Commissioning EL37x2 143 Version 3 5 Fig 185 Process data tab SM1 EL37x2...