Parameterization and commissioning
CX8095
57
Version: 1.5
3. Select ETHERNET MODULE "Generic Ethernet Module".
4. Enter the IP address from entry 8000:21. 129
dec
is entered for the input instance, 130
dec
for the output
instance and 128
dec
for the config instance.
The data length is dependent on the Comm format. In this sample INT was selected as the Comm for-
mat, therefore the number of data items from entries 8001:05 and 8001:07 must be divided once again
by 2, since these are specified in TwinCAT in bytes and on the RSLogix in Word length (INT).
If the number of bytes is an odd number it must be rounded up. This also applies even if the Comm
format is set to DINT, in which case you must round up to the next whole number.