Parameterization and commissioning
CX8095
54
Version: 1.5
ADS-Read command
AMSNetId:
Take the AMSNetId from the System Manager of the Ethernet/TP device.
Port:
In the case of the CX8095 the port number is to be permanently set to 0xFFFF.
Slave:
IDXGRP: 0x44818000
IDXOFFS: ID of the slave interface
LEN: 256
The ID of the slave is displayed in the TwinCAT System Manager on the "Configuration" tab. The ID is set by
the system and can only be read.
Master:
IDXGRP: 0x4481F800
IDXOFFS:0x00000000
LEN: 256
The data are saved in the data array as described above.
CX8095 example for TwinCAT 2.11 R3 build 2254 in order to change the IP address from the PLC:
https://infosys.beckhoff.com/content/1033/cx8095_hw/Resources/zip/2125688459.zip