Parameterization and commissioning
4
Parameterization and commissioning
4.1
Address switch
Address switch S101/S102
The address switch can be read internally from the PLC. The function F_CX80XX_ADDRESS is used for this
purpose. The switch has no purpose for the serial interfaces.
2-pole DIP switch (under the flap between the battery and the SD card slot)
Requirements
DIP switch (red)
Meaning
1 off and 2 off
normal mode, TwinCAT is started
1 on and 2 off
The CX mode starts in Config Mode; the flash
memory or, in the case of the CX80xx the SD card, is
reachable via the USB interface (for example for an
image update).
1 off and 2 on
Restore the registry
1 on and 2 on
No function so far
4.2
Setting the IP adress
4.2.1
IP address
The CX8010, CX803x, CX805x and CX8080 have an Ethernet interface, X001.
X001
IP addressing via the operating system; default is DHCP (represented in the operating system as FEC1)
EtherCAT interface
The EtherCAT interface is a further Ethernet interface that is not visible in the operating system for the IP
addressing.
CX8080
21
Version: 1.0.0