Programming
CX8030 / CX8031
61
Version: 1.6
Manufacturer-specific diagnosis
The structure of the manufacturer-specific diagnosis may be found in the documentation for the DP slave.
7.4.1.4
Uploading the Configuration
During operation the PROFIBUS can be scanned for new devices via
Read:
ADS-Read parameters
Meaning
Net-ID
Net-ID of the master (see the device's
Port
200
IndexGroup
0x00yyF830 (yy = station address, Beckhoff devices
provide the same information as other devices)
IndexOffset
0
Length
1538
Data
Configuration data of the slave
If the device is from another manufacturer, or if the IndexGroup indicates that Beckhoff devices are to
behave in exactly the same way as devices from other manufacturers, then the following information is
returned in the ADS read response:
Offset
Description
0 -1
1
2 - 7
DP diagnostic data bytes 0-5 (see
)
8 - 251
DP configuration data (
CfgData
)