Commissioning

CP39xx

28

Version: 3.1

Fig. 20: CP39xx_cable duct

The cables for the push button extension C9900-G02x run through the mounting arm tube into the mounting
arm adapter and onwards through the cable duct into the push button extension. You have to open both the
cable duct and the push button extension in order to route the cables.

To open the cable duct, follow the steps below as shown in Figure 21:

1. Remove the four Torx TX10 screws from the cable duct (section A).

2. Remove the cover of the cable duct (section B).

A

B

Fig. 21: CP39xx_opening the cable duct

To open the push button extension, follow the steps below as shown in Figure 22:

1. Remove the seven Torx TX10 screws from the push button extension (section A).

2. Remove the cover of the extension (section B).

Summary of Contents for CP39 Series

Page 1: ...Manual EN CP39xx Control Panel 9 22 2021 Version 3 1...

Page 2: ......

Page 3: ...ink 4 input 16 3 4 Optional USB interface 19 3 5 Name plate 20 3 6 Connection cables connection kits 21 3 6 1 CP39xx 0000 connection kits 21 3 6 2 CP39xx 0010 connection cable 22 4 Commissioning 24 4...

Page 4: ...Table of contents CP39xx 4 Version 3 1...

Page 5: ...gurations depicted may deviate from the standard Trademarks Beckhoff TwinCAT TwinCAT BSD TC BSD EtherCAT EtherCAT G EtherCAT G10 EtherCAT P Safety over EtherCAT TwinSAFE XFC XTS and XPlanar are regist...

Page 6: ...OTE Disregarding the notice may lead to damage to property 2 2 Intended use The CP39xx multi touch Control Panel is designed for industrial applications in machine and plant engineering A display with...

Page 7: ...engineering background operate the device Use by unauthorized persons can lead to damage to property and loss of data Protect the power supply cable with a fuse with a max rating of 16 A The fuse ser...

Page 8: ...touch Aluminum housing with glass front IP65 all round the housing surface is electrically insulating CP39xx 0000 interfaces 1x DVI Extended input 1x USB Extended input CP39xx 0010 interfaces 1x CP L...

Page 9: ...nel PCs CP3x12 to CP3x24 with integrated USB IP65 socket on the rear side C9900 M423 Toolboard for keyboard and mouse or tools mounted on the underside of a Control Panel or Panel PCs CP3x12 to CP3x24...

Page 10: ...herwise there are no differences in the external design of the device 1 2 3 4 Fig 3 CP39xx_configuration Table 2 CP39xx configuration legend No Component Description 1 Display and touch screen glass O...

Page 11: ...adapter with downwards orientation Follow the steps below as shown in Figure 5 1 Insert a flat blade screwdriver in the recesses on the underside of the mounting arm adapter section A 2 Bend the cove...

Page 12: ...4 x 0 75 mm2 can be accommodated For long supply lines use 4 x 0 75 mm2 cables to achieve a low voltage drop on the supply lines There should be at least 22 V at the power supply plug of the Control P...

Page 13: ...istortion of the graphics signal on arrival at the Control Panel A signal processor is used in the Control Panel to fully restore the DVI signal The Industrial PC requires a conventional DVI output X1...

Page 14: ...To realize a distance of 50 m without hubs USB Extended converts the USB signal so that it can be transmitted via a 50 m CAT 5 cable In the Control Panel the signal is converted back to USB This is no...

Page 15: ...the mounting arm adapter with upwards or downwards orientation The procedure is shown as an example for the mounting arm adapter with downwards orientation Follow the steps below as shown in Figure 10...

Page 16: ...ow voltage drop on the supply lines There should be at least 22 V at the power supply plug of the Control Panel so that the Control Panel remains switched on during voltage fluctuations The plug is in...

Page 17: ...C is connected to the transmitter box via USB and DP DVI The transmitter box is then connected to the Control Panel via the CP Link 4 connection of the transmitter box using a CP Link 4 cable USB and...

Page 18: ...to DVI Fig 15 CP39xx 0010_CP Link 4 CU8803 The following ordering options are available for the transmitter boxes CU8802 0000 The DVI to DVI cable is included with the box CU8802 0001 The DisplayPort...

Page 19: ...16 shows the interface on the mounting arm adapter A and on the connection block B A B Fig 16 CP39xx_optional USB interface The interface is located under a screw cap with IP65 protection class This i...

Page 20: ...indicate the product version 2 Serial number BTN 3 Date of manufacture 4 Display 5 Touch screen 6 Power supply 24 VDC NEC class 2 7 Note be sure to read the manual of the device 8 Symbols Note Here a...

Page 21: ...verter for DIN rail mounting next to the PC and 1 m USB cable for connecting the USB to USB E 2 0 converter to the PC C9900 K649 15 m connection kit for CP39xx 0000 consisting of 15 m DVI cable 15 m C...

Page 22: ...15 m one end with IP 65 connector for Control Panel CP39xx 0010 or CPX39xx 0010 C9900 K654 RJ45 connection cable CAT 6A 20 m one end with IP 65 connector for Control Panel CP39xx 0010 or CPX39xx 0010...

Page 23: ...707 RJ45 connection cable CAT 6A 30 m one end with IP 65 connector for Control Panel CP39xx 0010 or CPX39xx 0010 drag chain suitable C9900 K708 RJ45 connection cable CAT 6A 40 m one end with IP 65 con...

Page 24: ...dhesive protective film for Panel PCs and Control Panels with 7 inch display for fitting onto the glass pane 1 item C9900 T226 Adhesive protective film for Panel PCs and Control Panels with 12 inch di...

Page 25: ...r Panel PCs and Control Panels with 21 5 inch display for fitting onto the glass pane ex works C9900 T224 Adhesive protective film for Panel PCs and Control Panels with 24 inch display for fitting ont...

Page 26: ...to the device Protect the device against moisture condensation during transport in cold weather or in case of ex treme temperature fluctuations Do not put the device into operation until it has slowly...

Page 27: ...for Rittal and Rolec mounting arm systems with 48 mm tube from above C9900 M751 Rotatable and tiltable mounting arm adapter on Control Panel CP3912 to CP3924 for Rittal and Rolec mounting arm systems...

Page 28: ...nd the push button extension in order to route the cables To open the cable duct follow the steps below as shown in Figure 21 1 Remove the four Torx TX10 screws from the cable duct section A 2 Remove...

Page 29: ...other tools you need a hook wrench for the installation You can order this from your Beckhoff Sales using the following order identifier C9900 Z263 Hook wrench size 58 62 for tying up the slotted nut...

Page 30: ...Commissioning CP39xx 30 Version 3 1 The mounting arm adapter facilitates tilting of the Control Panel fitted to the mounting arm tube by 20 and rotate it by 165...

Page 31: ...power supply unit is required to supply 24 V DC 15 20 for operating the device Connect the Control Panel in the control cabinet according to standard EN 60204 1 2006 Protective Extra Low Voltage PELV...

Page 32: ...nductor Protective earth By connecting the PE protective earth you establish the low resistance protective earthing of the Control Panel and thus avoid dangerous touch voltages EMC NOTE Hardware damag...

Page 33: ...cables 2 far left on the strain relief rail by fixing both cables together with one cable tie Use the left and the third tab from the left For the CP39xx 0010 section B you have to route all cables i...

Page 34: ...urther to the outside to a strain relief plate in addition to the strain relief rail see fig 27 To do this pull the cable through under the plate and then fasten the cable to the plate with cable ties...

Page 35: ...apter In the case of the M20 cable gland the device version is additionally decisive for the position of the cable gland CP39xx 0000 C9900 G02x CP39xx 0010 C9900 G02x CP39xx 0000 C9900 G05x Fig 28 CP3...

Page 36: ...a low voltage drop on the supply line There should be at least 22 V at the voltage connector of the Control Panel so that the Panel remains switched on during voltage fluctuations Proceed as follows...

Page 37: ...x 0010 with CP Link 4 and CU8803 transmitter box you only have to pay attention to the voltage on the supply line to the transmitter box More detailed information can be found in the manual for the CU...

Page 38: ...shock Never disconnect the cables of the Control Panel during a thunderstorm NOTE Hardware damage due to power supply Disconnecting the CP Link 4 connection while the transmitter box power supply is...

Page 39: ...Torx TX20 screw of the strain relief rail section A 3 Rotate the strain relief rail by 180 to the left section B B A Fig 31 CP39xx_releasing the strain relief rail Disconnect the power supply Proceed...

Page 40: ...sure the Control Panel is secured against falling down before you undo the cap nut of the mount ing arm adapter To remove the Control Panel from the mounting arm tube follow the steps shown in Fig 24...

Page 41: ...ecommissioning CP39xx 41 Version 3 1 1 2 Fig 33 CP39xx_Toolboard and handle Disposal of the Control Panel When disposing of the Control Panel the national electronic waste regulations must be followed...

Page 42: ...ning agents Examples include benzine spirit acetone Glass cleaner Avoid the following cleaning agents Detergents with scouring or abrasive components Metal cleaning objects such as razor blades or ste...

Page 43: ...mode The period can be set between 5 and 120 seconds Right click the sun symbol again and click Options Now select the appropriate period see fig 35 Fig 35 CP39xx_Configuration Cleaning Mode Repair O...

Page 44: ...g functional earth of the device Poor or missing ground connection of the user Check potential equalization and grounding measures Touch the Control Panel frame and check the touch function at the sam...

Page 45: ...3919 max 25 W CP3921 max 27 W CP3924 max 34 W Protection class IP65 Vibration resistance sinusoidal vibration EN 60068 2 6 10 58 Hz 0 035 mm 58 500 Hz 0 5 G 5 m s2 Shock resistance shock EN 60068 2 27...

Page 46: ...919 max 31 W 46 W CP3921 max 33 W 48 W CP3924 max 40 W 55 W Protection class IP65 Vibration resistance sinusoidal vibration EN 60068 2 6 10 58 Hz 0 035 mm 58 500 Hz 0 5 G 5 m s2 Shock resistance shock...

Page 47: ...n find on the name plate Beckhoff Support Support offers you comprehensive technical assistance helping you not only with the application of individual Beckhoff products but also with other wide rangi...

Page 48: ...ing part 15 of the FCC regulations These limits are designed to provide adequate protection against adverse interference if the device is used in a commercial environment This device generates uses an...

Page 49: ...P39xx_optional USB interface 19 Fig 18 CP39xx_name plate 20 Fig 19 CP39xx_Mounting arm adapter options 27 Fig 20 CP39xx_cable duct 28 Fig 21 CP39xx_opening the cable duct 28 Fig 22 CP39xx_opening the...

Page 50: ...nput pin assignment 14 Table 6 Voltage socket pin assignment 16 Table 7 CP Link 4 pin assignment 16 Table 8 USB interface pin assignment 19 Table 9 Legend for CP39xx name plate 20 Table 10 CP39xx 0010...

Page 51: ......

Page 52: ...Beckhoff Automation GmbH Co KG H lshorstweg 20 33415 Verl Germany Phone 49 5246 9630 info beckhoff com www beckhoff com More Information www beckhoff com cp39xx...

Reviews: