General operating conditions
The following conditions must be met in order to ensure flawless operation of the fieldbus components. Also
note the details in chapter "
".
Environmental conditions
Operation
The components may not be used without additional protection in the following locations:
• in difficult environments, such as where there are corrosive vapours or gases, or high dust levels
• in the presence of high levels of ionizing radiation
Condition
Permissible range
Permissible ambient temperature during
operation
-25°C ...+60°C
Relative humidity during operation
95 %, no condensation
Installation position
variable
Vibration resistance
conforms to EN 60068-2-6
Shock resistance
conforms to EN 60068-2-27, EN 60068-2-29,
see also
installation instructions for enhanced mechanical
EMC resistance
conforms to EN 61000-6-2
Emission
conforms to EN 61000-6-4
Transport and storage
Condition
Permissible range
Permissible ambient temperature during
storage
-40°C... +85°C
Relative humidity
95 %, no condensation
Free fall
up to 1 m in the original packaging
Protection classes and types
Condition
Permissible range
Protection class in accordance with IEC 536
(VDE 0106, Part 1)
A protective conductor connection to the mounting rail is
necessary!
Protection class conforms to IEC 529
IP20 (protection against contact with a standard test finger)
Protection against foreign objects
Less than 12 mm in diameter
Protection against water
no protection