Parameterization and commissioning
BK11x0, BK1250
78
Version: 4.1
Step 3:
After the KS2000 software has been started and the ADS communication channel has been
activated ("Options", "Communication channel", "ADS"), enter the AmsServerNetId specified in the TwinCAT
System Manager under "Mailbox", "ADS Info" (Fig.
TwinCAT System Manager: dialog "Mailbox", transferring
the AmsServerNetID
) in the pull-down menu of the "ADS" tab (Fig.4):
•
Existing device:
If you select an existing device under Name
(1)
, the AmsServerNetId
(2)
is entered
automatically. The AdsPort setting ("100")
(3)
should not be changed. Click on
Test
(4)
to check the
connection settings.
•
User Defined:
For User Defined the AmsServerNetId has to be entered manually
(2)
. Click on
Test
(4)
to check the connection settings.
Fig. 56: TwinCAT System Manager: "Mailbox" dialog, transfer of AmsServerNetID
Fig. 57: KS2000: "ADS" tab, enter the AmsServerNetID