Drive / tubular drive operation
•
The control unit is ideally designed for tubular drives with internal limit switches that
switch off the corresponding direction of travel directly. The control unit evaluates
the drive current and can thus identify the limit positions.
•
Operation with external limit switches is possible. External limit switches must be
approved for 230 V and be able to switch the drive current. The connection is es-
tablished in the corresponding drive cable. The installation must be 230 V capable.
When operated with tubular drives, the internal limit switches must be set so that
they do not trigger a deactivation at any point on the required travel distance! To do
this, the switch-off point can be set approx. 3 revolutions before the starting point
and after the end of the travel distance.
Attention
When operating with external limit switches, special atten-
tion must be paid to the safety regulations!
Panic function
•
When the "panic function" is active and the door is in motion, the door travel stops
the first time the input is actuated. The second time the input is actuated, the door
starts moving in the actuated direction.
•
If actuation occurs when the door is running in the opposite direction and a "panic
function" is not set, the door stops and immediately starts moving in the opposite
direction. If actuation occurs in the same direction (current travel direction), this
has no effect.
Automatic reclosing
•
If the door is not in the CLOSE limit position, the automatic reclosing operation
takes effect after the stay-open time expires [M.A6]. The warning light output is
active for the set advance warning time [M.b0] before the door travels to the
CLOSE limit position.
•
If the door is in the OPEN limit position, only the stay-open time is reset via a pulse
or OPEN command. The stay-open time remains reset for as long as a pulse or
OPEN command is applied. The stay-open time only starts to run down when an
OPEN/pulse command is no longer applied.
•
When the automatic reclosing is active, a pulse command always effects travel in
the OPEN direction. The same applies if the door is already travelling in the CLOSE
direction. The stay-open time restarts.
•
Commands for specific OPEN / CLOSE are also effective when the automatic re-
closing is active.