Tab.43
Parameter
Description
Factory setting
EHC–06
Factory setting
SCB-04
AP001
BL input function selectionBL1 :
1 = Full blocking of the installation – frost protection not guaran
teed
2 = Partial blocking of the installation – installation frost protection
3 = User reset locking
4 = Backup relieved
5 = Generator relieved
6 =Gen.&Backup relieved
7 = High, Low Tariff
8 =Photovoltaic HP Only
9 =PV HP And backup
10 = Smart Grid ready
11= heating/cooling
2
not available
AP028
Configuration of the cooling mode
0 = Off
1 = Active cooling on
2 = Free cooling on, not used
0
not available
AP006
Appliance will report low water pressure below this value
Can be set from 0 bar to 6 bar
0.3
not available
AP010
Select the type of service notification
0 = None
1 = Custom notification
2 = ABC notification,
0
not available
AP011
Hours powered to raise a service notification
Can be set from 0 Hours to 65534 Hours
8700
not available
AP056
Enable outdoor sensor
not available
1
AP058
Warning message indicating that pressure is low
Can be set from 0 bar to 2 bar
0.8
not available
AP063
Maximum central heating flow temperature setpoint
Can be set from 20 °C to 75 °C
Electrical back-
up: 75
not available
AP073
Outdoor temperature: upper limit for heating
22
22
AP075
Temperature variance from set outdoor upper temp. limit in which
the generator will not heat or cool
Can be set from 0 to 10 °C
4
4
AP079
Inertia of the building used for heat up speed
Can be set from 0 to 10
0 = 10 hours for a building with low thermal inertia,
3 = 22 hours for a building with normal thermal inertia,
10 = 50 hours for a building with high thermal inertia.
Modification of the factory setting is only useful in exceptional cases.
3
3
AP080
Outside temperature below which the antifreeze protection is
activated:
can be set from -29 to 20 °C
set to -30 °C = function deactivated
3
3
AP091
Outdoor sensor type
0 =Auto
0
0
AP098
BL1 input contact configuration
0 = input active on Open contact
1 = input active on Closed contact
0
not available
AP099
BL2 input contact configuration
0 = input active on Open contact
1 = input active on Closed contact
0
not available