1. Connect the swimming pool secondary pump to the terminal block.
2. Connect the swimming pool temperature sensor to the TFlow terminal
block.
3. Connect the swimming pool primary pump to the
terminal block.
4. Connect the swimming pool heating cut-off control to the R-Bus
terminal block.
8.4.2
Configuring swimming pool heating
1. Go to the Installer menu.
2. Access the Installer menu by entering the code 0012 by pressing the
and keys.
3. Confirm access by pressing the
key.
4. Access the circuit B and SCB-04 PCB parameters by pressing the
or key.
5. Confirm the selection by pressing the
key.
6. Configure the following parameters:
Tab.73 Heating configuration for a swimming pool
Parameter
Description
Value to be set
CP020
Circuit type
3
CP540
Swimming pool water temperature set point
26 °C
Important
Back-up operation follows the same logic as heating mode. If
necessary, it is possible to block operation of the back-ups with
the BL inputs.
Fig.110
MW-6000381-7
1
2
3
4