Fig.67
MW-6000807-01
1
2
1
2
A
B
1 Power supply
2 Communication bus
Connecting the AWHP 4.5 MR unit
The electrical connection of the outdoor unit must be made via a dedicated
circuit. Before connecting, check that the cross-section of the cable and
the circuit breaker on the electric panel are suitable.
1. Remove the service panel.
2. Remove the earth connection present on the appliance and discard.
3. Place the stripped part of the earth wire
on the screw with the
square washer provided.
Danger
The earth wire must be 10 mm longer than the N and L wires.
4. Secure the screw with the earth wire on the chassis. Ensure that the
earth wire is correctly placed under the washer, in contact with the
chassis.
5. Connect the other wires to the appropriate terminals.
6. Feed the cable into the cable duct and adjust the length of the cable
accordingly. Lock it in position using the traction arrester device.
7. Put the service panel back in place.
Connecting the AWHP 6 MR-3 unit
The electrical connection of the outdoor unit must be made via a dedicated
circuit. Before connecting, check that the cross-section of the cable and
the circuit breaker on the electric panel are suitable.
Fig.68
MW-6000808-01
1
2
Fig.69
230V~
MW-1000788-2
NEW
3
4
5
6
230V~
L
N
10mm
5 Installation
54
7654506 - v06 - 19112019