INSTRUCTIONS PERTAINING TO THE INSTALLER
925.492.2
15.2 LAS FLUE DUCT INSTALLATION OPTIONS
15.3 VERTICAL FLUE TERMINAL INSTALLATION OPTIONS
This type of installation can be carried out both on a fl at or pitched roof by fi tting a terminal, an appropriate weathering tile
and sleeve, (supplementary fi ttings supplied on demand).
For detailed instructions concerning the installation of fi ttings refer to the technical data accompanying the fi ttings.
1
4
6
1
G
C /
8
0
9
0
_
3
0
5
0
L max = 4 m
L max = 2 m
L max = 3 m
1
5
0 2
_
2 0
0 2
L max = 4 m
SEPARATED FLUE-AIR DUCTING
This type of ducting allows to disengage exhaust fl ue gases both outside the building and into single fl ue ducts.
Comburant air may be drawn in at a different site from where the fl ue terminal is located.
The splitting kit consists of a fl ue duct adaptor (100/80) and of an air duct adaptor.
For the air duct adaptor fi t the screws and seals previously removed from the cap.
The fl ue duct must not fall and all horizontal runs must always rise at approximately 3° from the boiler.
Consideration for protection to exposed parts of the outlet duct where accidental touch may occur must be given.
Calculation of the total equivalent length:
The total equivalent length depends on the number and type of components in the fl ue system.
The total equivalent length is the addition of Air Duct Value + Flue Duct Value, plus the equivalent length of any bends.
The bend equivalences are:
45° = 0.25m
90° = 0.50m
ASSEMBLING THE FLUE SYSTEM
The pipe extensions can be cut to length if necessary. The cut end should be de-burred to prevent damage to seals when
assembling to a fi tting.
Apply soap solution to all seals to aid assembly.
Always use 80mm pipe clamps to secure/support the ducts. Secure the roof terminal with the pipe clamp supplied.
L max =
4 m
240 Fi
L max =
3 m
310 Fi