INSTRUCTIONS FOR FITTERS
22. GAS CONVERSION
To calibrate the gas valves, enable the calibration function as described in section 22.1 and carry out the following ope-
rations:
1) Calibrating maximum heat output.
Check that the CO2 measured on the flue duct, with the boiler operating at maximum heat capacity, matches that in-
dicated in table 1. If it does not, turn the adjustment screw (V) on the gas valve. Turn the screw clockwise to decrease
the level of CO2 and clockwise to increase it.
2) Calibrating reduced heat output.
Check that the CO2 measured on the flue duct, with the boiler operating at minimum heat capacity, matches that in-
dicated in table 1. If it does not, turn the adjustment screw (K) on the gas valve. Turn the screw clockwise to increase
the level of CO2 and anticlockwise to decrease it.
0310_0114
Figure 16
Pi:
gas inlet pressure tap
P out:
gas at burner pressure tap
P:
OFFSET measurement pressure tap
Pl:
air from fan signal input
V:
gas flow adjustment screw
K:
OFFSET adjustment screw
IMPORTANT:
when converting from natural gas to propane (LPG),
before calibrating the gas valve, as described above, perform the fol-
lowing operations:
• Turn the adjustment screw
(V)
on the gas valve for the number of
complete turns indicated in table 3;
• Use the
AVS 77
climate controller to set parameters
608
and
611
relative to ignition power, as described in section 21. Table 3 shows
the correct values to set.
22.1 ENABLING THE CALIBRATION FUNCTION
CAUTION
if the heating system comprises a single zone at low temperature, set parameter “CHSL” to 45°, as described in section 30.
Access the electronic board programming mode as indicated in section 21.
• Scroll the list of parameters and select parameter
OF 555.0
;
• Set parameter
OF 555.0 = 1
and press
OK
(the function is enabled);
To rapidly set maximum or minimum boiler power, proceed as follows:
• Scroll the list of parameters again and select parameter
OF 677
;
• Set parameter
OF 677 = 100%
and press
OK
; (the boiler will rapidly reach maximum capacity)
• Set parameter
OF 677 = 0%
and press
OK
; (the boiler will rapidly reach minimum capacity)
• Then calibrate the gas valve as described in points 1 and 2 of section 22.
N.B.:
the
CALIBRATION
function lasts 15 minutes, after which it automatically terminates. To exit the function before
calibration has finished, set parameter OF 555.0 = 0 or switch off the boiler.
Summary of Contents for LINA 3 COMFORT HT
Page 131: ...131 926 420 3 RU 3 BAXI CLOW AVS 77 5 12 3 2 3 3 1 0702_2404 4 4 0702_2405 3 2...
Page 133: ...133 926 420 3 RU 3 4 1 3 1 1 t 1 HW SP 3 4 1 IP PROG 1 3 5 PROG OK OK Day 1 7 IP 3 6 1 4 4 3 6...
Page 138: ...138 926 420 3 RU 10 10 45 90 02 2 47 47 DD 02 2 45 1 4 4 2 PARTY MAN 60 4 4 1 0703_0507 60...
Page 150: ...150 926 420 3 RU 11 1 a b 11 2 2 11 3 1 2 4 17 17 2 0705_1602 M2 18 3 4 12 0605_1604 M2...
Page 153: ...153 926 420 3 RU 20 14 AVS 77 16 14 AVS 77 0709_0701 CG_1933 1 AVS 77 1 1 2 3 N...
Page 158: ...158 926 420 3 RU OK 9 1 110 OK 9 1 90 OK 9 1 0 5 3 5 30 0 5 24 10 24 3 0 1 1 0 23...
Page 167: ...167 926 420 3 RU 0901_1506 CG_1934B 32 N R G V B V HT 280 HT 330 NTC RESET NTC...
Page 168: ...168 926 420 3 RU 0901_1503 CG_2056 HT 1 120 HT 1 240 HT 1 280 N R G V B V RESET NTC...
Page 344: ...344 926 420 3 EL GR 4 2 3 1 2 COOL 31 COOL 31 3 2 COMFORT 3 6 ff 3 3 25 25 50 50 75 75 100...
Page 362: ...362 926 420 3 EL GR E 11 1 a b 11 2 M2 3 1 2 4 C 17 17 2 0705_1602 M2 18 3 4 12 0605_1604 M2...
Page 365: ...365 926 420 3 EL GR 20 14 0709_0701 CG_1933 1 AVS 77 AVS 77 16 14 AVS 77 1 1 2 3 N...
Page 370: ...370 926 420 3 EL GR OK 9 1 NTC 110 C OK 9 1 90 C OK 9 1 0 5 bar 3 5 C 30 C 24 10 24 3 bar 0 23...
Page 376: ...376 926 420 3 EL GR AMBON RMOD EXT T AMBON RMOD EXT T 0 0 COMFORT 1 1 1 1 0...
Page 382: ...382 926 420 3 EL GR...
Page 383: ...383 926 420 3 EL GR...