![Baxi CPA 1045-BT Installation, Assembly, And Operating Instructions For The Installer Download Page 31](http://html1.mh-extra.com/html/baxi/cpa-1045-bt/cpa-1045-bt_installation-assembly-and-operating-instructions-for-the-installer_2711735031.webp)
31
CPA
290-BT
CPA
345-BT
CPA
395-BT
CPA
465-BT
CPA
580-BT
CPA
695-BT
Fuels
Oil C, PCI=10.200 Kcal/Kg; viscosity máx 7 mm2/s ;
Natural Gas, PCI=9.300 Kcal/Nm3 ; Propan Gas, PCI=22.300 Kcal/Nm3
Nominal heat output
kW
290
345
395
465
580
695
Heat input
kW
315,2
374,6
427,9
504,3
627,7
752,9
Efficiency at 100% full load and 70°C average temperature
%
92,0
92,1
92,3
92,2
92,4
92,3
Efficiency at 30% full load and 40°C average temperature
%
93,0
93,1
93,0
93,2
93,2
93,1
Water content
L
272
297
311
453
503
689
Maximum working pressure
bar
5
5
5
5
5
5
Set temperature range
°C
50-90
50-90
50-90
50-90
50-90
50-90
Fuel comsumption
Oil
Kg/h
26,58
31,58
36,08
42,52
52,92
63,48
Gás Natural
Nm3/h
29,15
34,64
39,57
46,63
58,05
69,62
Gás Propano
Nm3/h
12,16
14,45
16,50
19,45
24,21
29,04
Flue gases (1):
Evacuation system
B23
B23
B23
B23
B23
B23
Mass flue gas flow with Oil
kg/s
0,132
0,157
0,179
0,211
0,263
0,315
Mass flue gas flow with Gas
kg/s
0,143
0,170
0,194
0,229
0,285
0,342
Combustion chamber overpressure
mbar
2,5
2,8
3,2
3,5
4,1
4,6
Flue gases temperature
°C
172
172
170
172
170
170
Combustion chamber volume
m
3
0,290
0,328
0,353
0,421
0,486
0,620
Pressure at chimney base
mbar
≤
0
≤
0
≤
0
≤
0
≤
0
≤
0
Waterside pressure drop:
with Δ
D
T=10°C
mbar
42,7
56,2
74,2
58,5
78,7
60,7
with Δ
D
T=20°C
mbar
10,7
14,0
18,5
14,6
19,7
15,2
Recommended BAXI burner with Oil (to be ordered separately)
2 stage operation
Tecno 34-L
Tecno 44-L
Tecno 50-L
Tecno 50-L
Tecno 70-L
Tecno 70-L
Modulating operation
-
-
Tecno 50-LM
Tecno 50-LM
Tecno 70-LM
Tecno 70-LM
Recommended nozzle with Oil burners
2 stage operation, Delavan W
GPH
2 x 3,50 - 60°
2 x 4,00 - 60°
2 x 4,50 - 60°
2 x 5,50 - 60°
2 x 6,50 - 60°
2 x 8,50 - 60°
Modulating operation, Bergonzo A3
Kg/h
-
-
50 - 45°
60 - 45°
60 - 45°
70 - 45°
Recommended BAXI burner with Gas (to be ordered separately)
2 stage operation
Crono 30-G2
Tecno 44-G
Tecno 44-G
Tecno 50-G
Tecno 70-G
Tecno 70-G
Modulating operation
Tecno 34-GM
Tecno 44-GM
Tecno 44-GM
Tecno 50-GM
Tecno 70-GM
Tecno 70-GM
Water flow at nominal output
with Δ
D
T=10°C
m3/h
24,94
29,67
33,97
39,99
49,88
59,77
with Δ
D
T=20°C
m3/h
12,47
14,84
16,99
20,00
24,94
29,89
Noise level (3) (4)
Oil fuel
dB(A)
70
72
75
75
75
75
Gas fuel
dB(A)
70
72
72
72
75
75
Stanby losses at
Δ
T=30 °K
W
840
905
980
1040
1155
1270
Net weight
Kg
588
645
695
835
940
1180
Minimum return temperature with Oil/Gas fuel (2)
°C
37 / 40
Emissions (1),(4):
Oil fuel NOx / CO
mg/kWh
<180 / <70
Gas fuel NOx / CO
mg/kWh
<120 / <40
Electrical supply to boiler control panel
monophasic 230 V (+10%-15%) - 50 Hz
Grade of protection
IP20
(1) At nominal output, 20% air excess, boiler average water temperature 70°C and ambient temperature 25°C.
(2) Burner with 2-stages operation with 1st stage set to 50% of the nominal output or modulating operation with 50-100% output range. More details in
section “Prevention of condensations”.
(3) Sound pressure mesured 1m distance front the boiler at nominal output.
(4) With recommended BAXI burner.
Tab. 1
Summary of Contents for CPA 1045-BT
Page 33: ...33...