30
CPA
55-BTH
CPA
70-BTH
CPA
100-BTH
CPA
130-BTH
CPA
170-BTH
CPA
220-BTH
Fuels
Oil C, PCI=10.200 Kcal/Kg; viscosity máx 7 mm2/s ;
Natural Gas, PCI=9.300 Kcal/Nm3 ; Propan Gas, PCI=22.300 Kcal/Nm3
Nominal heat output
kW
55
70
100
130
170
220
Heat input
kW
58,5
74,4
106
137,6
179,3
231,8
Efficiency at 100% full load and 70°C average temperature
%
94,0
94,1
94,3
94,5
94,8
94,9
Efficiency at 30% full load and 40°C average temperature
%
94,8
94,7
95,2
95,5
95,7
95,9
Water content
L
130
150
170
180
195
270
Maximum working pressure
bar
5
5
5
5
5
5
Set temperature range
°C
50-90
50-90
50-90
50-90
50-90
50-90
Fuel comsumption
Oil
Kg/h
4,93
6,27
8,94
11,60
15,12
19,54
Natural Gas
Nm3/h
5,59
8,12
11,63
15,17
18,65
23,12
Propan Gas
Nm3/h
2,33
3,39
4,85
6,33
7,78
9,64
Flue gases (1):
Evacuation system
B23
B23
B23
B23
B23
B23
Mass flue gas flow with Oil
kg/s
0,025
0,031
0,044
0,058
0,075
0,097
Mass flue gas flow with Gas
kg/s
0,027
0,040
0,057
0,074
0,092
0,113
Combustion chamber overpressure
mbar
0,3
0,5
0,6
0,9
1,3
1,6
Flue gases temperature
°C
135
135
133
130
125
125
Combustion chamber volume
m
3
0,112
0,132
0,179
0,198
0,220
0,290
Pressure at chimney base
mbar
≤
0
≤
0
≤
0
≤
0
≤
0
≤
0
Waterside pressure drop:
with Δ
D
T=10°C
mbar
11,2
11,2
11,9
18,5
25,9
24,8
with Δ
D
T=20°C
mbar
2,8
2,8
3,0
4,6
6,5
6,2
Recommended BAXI burner with Oil (to be ordened separately)
1 stage operation
Crono 10-L
Crono 10-L
Crono 15-L
Crono 20-L
Crono 20-L
-
2 stage operation
Crono 10-L2
Crono 10-L2
Crono 15-L2
Crono 20-L2
Crono 20-L2
Crono 25-L2
Modulating operation
-
-
-
-
-
-
Recomended nozzle Delavan W
GPH
1,25 - 60°
1,50 - 60°
2,25 - 60°
3,0 - 60°
3,5 - 60°
2 x 2,0 - 60°
Recommended BAXI burner with Gas (to be ordened separately)
1 stage operation
Crono 8-G
Crono 8-G
Crono 15-G
Crono 15-G
Crono 20-G
-
2 stage operation
Crono 8-G2
Crono 8-G2
Crono 15-G2
Crono 15-G2
Crono 20-G2
Crono 30-G2
Modulanting operation
Crono 8-GM
Crono 8-GM
Crono 15-GM
Crono 15-GM
Crono 20-GM
Tecno 34-GM
Water flow at nominal output
with Δ
D
T=10°C
m3/h
4,73
6,02
8,60
11,18
14,62
18,92
with Δ
D
T=20°C
m3/h
2,37
3,01
4,30
5,59
7,31
9,46
Noise level (3) (4)
Oil fuel
dB(A)
61
61
64
64
64
71
Gas fuel
dB(A)
62
62
66
66
71
70
Stanby losses at
Δ
T=30 °K
W
495
570
635
705
770
840
Net weight
Kg
285
320
385
425
465
588
Minumum return temperature with Oil/Gas fuel (2)
°C
39 / 42
Emissions (1),(4):
Oil fuel NOx / CO
mg/kWh
<180 / <70
<160 / <60
Gas fuel NOx / CO
mg/kWh
<75 / <20
<110 / <20
Electrical supply to boiler control panel
monophasic 230 V (+10%-15%) - 50 Hz
Grade of protection
IP20
(1) At nominal output, 20% air excess, boiler average water temperature 70°C and ambient temperature 25°C.
(2) Burner with 2-stages operation with 1st stage set to 50% of the nominal output or modulating operation with 50-100% output range. More details in
section “Prevention of condensations”.
(3) Sound pressure mesured 1m distance front the boiler at nominal output.
(4) With recommended BAXI burner.
Tab. 1
Summary of Contents for CPA 100-BTH