Control Terminals
Manual
b maXX
®
BM1000
Document No. 5.07003.04
Baumüller Nürnberg GmbH
64
6.11
Keep control wiring as far away as possible from the power wiring and in separate con-
duits to avoid interference. If necessary let them cross only at 90º angle.
The device control wiring should be properly installed and not touch any live power wir-
ing or terminals.
ACI
Analog current input
Figure 35:
Analog current input
Impedance:
250
Ω
Resolution:
10 bits
Range:
4 to 20 mA =
0 to max. output frequency (
P0033
)
Selection:
P0801
,
P0809
,
P1359
Set-up:
P1128
to
P1132
AFM
Analog output meter
Figure 36:
Analog output meter
0 to 10 V, 2 mA
Impedance:
20 k
Ω
Output current
2 mA max.
Resolution:
8 bits
Range:
0 to 10 V
DC
Function:
P1162
and
P1163
ACM
Analog control signal (ground)
Ground for AVI, ACI, AFM
Terminal
symbol
Terminal function
Factory settings (NPN mode)
ON: connect to DCM
NOTE
If a filter is required for reducing EMI (Electro Magnetic Interference), install it as close as
possible to the device. EMI can also be reduced by lowering the carrier frequency.
When using a GFCI (Ground Fault Circuit Interrupter), select a current sensor with sensi-
tivity of 200 mA, and not less than 0.1-second detection time to avoid noise tripping.
Summary of Contents for b maXX BM1000
Page 1: ...E 5 07003 04 Manual b maXX BM1000 Basic unit ...
Page 108: ...Manual b maXX BM1000 Document No 5 07003 04 Baumüller Nürnberg GmbH 108 of 174 ...
Page 118: ...Manual b maXX BM1000 Document No 5 07003 04 Baumüller Nürnberg GmbH 118 of 174 A ...
Page 172: ...Manual b maXX BM1000 Document No 5 07003 04 Baumüller Nürnberg GmbH 172 of 174 Index ...
Page 174: ...Manual b maXX BM1000 Document No 5 07003 04 Baumüller Nürnberg GmbH 174 of 174 Notes ...
Page 175: ......