Technical data
Manual
b maXX
®
BM1000
Document No. 5.07003.04
147
D
D.5.1
Cable protection
The current-carrying capacity of conductors is determined in table 5 of EN60204-1. For your op-
eration you must determine the accordant value in the standard yourself, by taking into consid-
eration, amongst other things the cable mounting. Here you will find an extraction for the laying
of PVC- isolated cables on open cable racks:
Use suitable fuses with the enable characteristic gL or gR.
D.5.2
Cable prot device protection
Consider by your choice of the whole range fuses the current-carrying capacity connected
mains cables and the allowable maximum load of the device.
Recommended UL-listed fuses, see
B.4 Fuses for device-protection
D.6
Type of protection
D.7
Fire fighting appliances
Cable cross sec-
tion
Fuse
rated current
1.5 mm
2
16.1 A
2.5 mm
2
22 A
4 mm
2
30 A
Type of protection
IP 20
Fight fire with
ABC powder