EMD-RMTR.. User’s Manual
16
FS =
○ ○ ○ ○ ○
± ○ ○ ○ ○ ○
6.2.7 Flow Rspns
It means me of filter measure value. The long one can enhance the stability of flow display and output
digital, and fits for gross add up of pulse flow; the short one means fast respond rate, and fits for produc on
control.
6.3.8 Flow Direct
If users think the direct and design are differ, just change the direct parameter is OK, but not change
exci ng or signal.
6.2.9 Flow zero
Make sure the sensor is full of flow, and the flow is s llness. Flow zero is shown as velocity of flow, mm/s.
Converter’s zero-flow correction displays as below:
Upper small words: FS means measure value of zero;
Lower large words: correc on value of zero.
When FS is not “0”, please set FS = 0.
Note:
if change the value on next line and FS increases, please change the “+, -” to correct FS to zero.
Flow zero is the compound value of the sensor, and should be recorded in sensor list and band. The unit
will be mm/s, and the sign will be opposite with correc on value.
6.2.10 Flow cutoff
Flow cutoff is set in percentage of Upper Limit Range of flow, and users can delete all Negligible Small
Signals of flow volume, velocity and percentage out of displaying and outpu ng them. Some mes user can
delete output of current output signal and frequency (pulse) output signal only to have flow, velocity and
percentage being displayed.
6.2.11 Total Unit
Converter display is counter with 9 bits, and the max is 999999999.
Flow integrator value: 0.001L, 0.010L, 0.100L, 1.000L
0.001 m
3
, 0.010m
3
, 0.100 m
3
, 1.000 m
3
;