9287500995 Rev B
67
Specifications
BE2000E electrical and physical specifications are listed in the following paragraphs. The adjustment
increments shown apply to the PC software. Adjustment increments for the Front Panel Controls are
listed in the
Human-Machine Interface
chapter.
Operating Power
Single-Phase .............................. 180 to 240 Vac
Frequency Range ....................... 120 to 300 Hz
Burden ........................................ 330 VA
Terminals.................................... 3, 4
Generator Voltage Sensing
Type ........................................... 1-phase/3-phase, 4 ranges, 50/60 Hz
Terminals.................................... E1, E2, E3
Burden ........................................ <1 VA per phase
Range 1 ...................................... 120 Vac (100 to 140 Vac)
Range 2 ...................................... 240 Vac (200 to 280 Vac)
Range 3 ...................................... 480 Vac (400 to 560 Vac)
Range 4 ...................................... 600 Vac
Generator Current Sensing
Type ........................................... 1-phase (BØ), 50/60 Hz
Rating ......................................... 5 Aac maximum continuous
Burden ........................................ <0.1 VA
Terminals.................................... CT1, CT2
Contact Input Circuits
Type ........................................... Dry Contact
Interrogation Voltage .................. 13 Vdc
Terminals
Unit/Parallel Control ................... 52L, 52M
Raise .......................................... 6U, 7
Lower .......................................... 6D, 7
var/PF Enable ............................ 52J, 52K
Common Alarm Output
Type ........................................... Form A
Rated Load ................................. 7 Aac/7 Adc continuous
Make ........................................... 30 Aac/30 Adc, carry for 0.2 seconds
Break .......................................... 7 Aac/0.1 Adc
Operating Voltage ...................... 240 Vac/250 Vdc maximum
Terminals.................................... AL1, AL2
Field Output
Continuous Rating ...................... 75 Vdc, 3.0 Adc
10 Second Forcing Rating
200 Vac Power Input: ................. 150 Vdc, 7.5 Adc
Field Resistance: ........................ 18
Ω
minimum
Terminals:................................... F+, F
–
BE2000E
Specifications
Summary of Contents for BE2000E
Page 2: ......
Page 8: ...vi 9287500995 Rev B Contents BE2000E ...
Page 10: ...2 9287500995 Rev B General Information BE2000E ...
Page 28: ...20 9287500995 Rev B Figure 4 BE2000E Dimensions Installation BE2000E ...
Page 29: ...9287500995 Rev B 21 Figure 5 Cutout and Drilling Dimensions BE2000E Installation ...
Page 40: ...32 9287500995 Rev B Installation BE2000E ...
Page 68: ...60 9287500995 Rev B BESTCOMS Software BE2000E ...
Page 74: ...66 9287500995 Rev B Maintenance and Troubleshooting BE2000E ...
Page 80: ...72 9287500995 Rev B Revision History BE1 11f ...
Page 81: ......