46
9287500995 Rev B
Figure 28. Message Box to Return to FCR Nominal Setpoint
PF Tab
Figure 29 illustrates the settings, sensing values, and alarm signal indicators of the
PF
tab. Each setting
of the
PF
tab is described in the following paragraphs.
Figure 29. Analysis Screen, PF Tab
Power Factor Step Response - Power Factor Setpoint (Nominal).
This read-only field indicates the PF
setpoint. (The PF setpoint is set by using the
Setpoint
tab of the
Setting Adjustments
screen). The value
displayed in the PF Setpoint field is selected by clicking the adjacent button. Clicking this button sends the
PF Setpoint value to the BE2000E and changes the color of the button from gray to red.
Power Factor Step Response - Increment of PF setpoint.
This field indicates the increase that occurs to
the PF setpoint when the corresponding increment button is clicked. Any setpoint value within the range
and higher than setpoint value can be input to this filed. The PF setpoint changes to this value when the
adjacent button is clicked. When clicked, the
Increment
button changes from gray to red to indicate that
the PF setpoint has increased to the value in the field.
Power Factor Step Response - Decrement of PF setpoint.
This field indicates the decrease that occurs to
the PF setpoint when the corresponding
Decrement
button is clicked. Any setpoint value within the range
and lower than setpoint value can be input to this filed. The PF setpoint changes to this value when the
adjacent button is clicked. When clicked, the
Increment
button changes from gray to red to indicate that
the PF setpoint has decreased to the value in the field.
Pow
e
r Factor Step Response - Meter.
The meter in the
PF
tab shows the value selected. If a PF setpoint
value is sent by increase, decrease or setpoint button the meter shows the corresponding value and
BESTCOMS
™
Software
BE2000E
Summary of Contents for BE2000E
Page 2: ......
Page 8: ...vi 9287500995 Rev B Contents BE2000E ...
Page 10: ...2 9287500995 Rev B General Information BE2000E ...
Page 28: ...20 9287500995 Rev B Figure 4 BE2000E Dimensions Installation BE2000E ...
Page 29: ...9287500995 Rev B 21 Figure 5 Cutout and Drilling Dimensions BE2000E Installation ...
Page 40: ...32 9287500995 Rev B Installation BE2000E ...
Page 68: ...60 9287500995 Rev B BESTCOMS Software BE2000E ...
Page 74: ...66 9287500995 Rev B Maintenance and Troubleshooting BE2000E ...
Page 80: ...72 9287500995 Rev B Revision History BE1 11f ...
Page 81: ......