9287500995 Rev B
45
Figure 27. Analysis Screen, FCR Tab
Field Current Step Response - Increment of FCR Setpoint (A).
These two fields indicate the increase that
occurs to the FCR setpoint when the corresponding Increment button is clicked. The "% increase" field is
used to set and indicate the percentage that the FCR setpoint is increased when the Increment button is
clicked. The "FCR Setpoint =" field indicates the value of current that corresponds to the "% increase"
field. Any setpoint value within range and higher than setpoint value can also be typed into The "FCR
Setpoint =" field which updates the “% increase” field also. The FCR setpoint changes to this value when
the adjacent button is clicked. When clicked, the Increment button changes from gray to red to indicate
that the FCR setpoint has increased to the value in the "FCR Setpoint =" field.
Field Current Step Response - Decrement of FCR Setpoint (A).
These two fields indicate the change that
will occur to the FCR setpoint when the corresponding
Decrement
button is clicked. The "% decrease"
field is used to set and indicate the percentage that the FCR setpoint is decreased when the decrement
button is clicked. The "FCR Setpoint =" indicates the value of current that corresponds to the "%
decrease" field. Any setpoint value within range and lower than setpoint value can also be typed into The
"FCR Setpoint =" field which updates the “% decrease” field also. The FCR setpoint changes to this value
when the adjacent button is clicked. When clicked, the
Decrement
button changes from gray to red to
indicate that the FCR setpoint has decreased to the value in the "FCR Setpoint =" field.
Field Current Step Response - Meter.
The meter in the
FCR
tab shows the value selected. If an FCR
setpoint value is sent by increase, decrease or setpoint button the meter shows the corresponding value
and meter value text box also displays it. Any value within the range can either be input to meter value
text box or selected by dragging the pointer in the meter, using mouse. This value can then be sent to the
unit by pressing
Send
button.
The setpoint value currently set in the unit by any of the above methods is displayed in the current
setpoint textbox. To return to the nominal setting the button adjacent to
FCR Setpoint (I) (Nominal)
should
be pressed. If the
FCR Analysis
screen is left without returning to nominal setpoint a message box is
shown (Figure 28) which allows the user to return to nominal setpoint by pressing
YES
or remain at the
current setpoint by pressing
NO
.
BE2000E
BESTCOMS
™
Software
Summary of Contents for BE2000E
Page 2: ......
Page 8: ...vi 9287500995 Rev B Contents BE2000E ...
Page 10: ...2 9287500995 Rev B General Information BE2000E ...
Page 28: ...20 9287500995 Rev B Figure 4 BE2000E Dimensions Installation BE2000E ...
Page 29: ...9287500995 Rev B 21 Figure 5 Cutout and Drilling Dimensions BE2000E Installation ...
Page 40: ...32 9287500995 Rev B Installation BE2000E ...
Page 68: ...60 9287500995 Rev B BESTCOMS Software BE2000E ...
Page 74: ...66 9287500995 Rev B Maintenance and Troubleshooting BE2000E ...
Page 80: ...72 9287500995 Rev B Revision History BE1 11f ...
Page 81: ......