9287500995 Rev B
35
After initial governor adjustments are complete, reinstall the 5-ampere fuse, and connect only the power
input leads or PMG leads to the regulator. Remove all other regulator connections that may be present
and temporarily insulate them.
Start and run the generator at rated speed. The regulator will perform the self-test and enter a shutdown
mode. At this time, initial adjustments can be made.
After the initial adjustments are made, shut down the generator and connect the remaining regulator
leads. The generator may be started and final adjustments may be performed on the regulator.
Establishing Communication
Communication between BESTCOMS-BE2000E and the BE2000E must be established before viewing
metering values or reading or changing settings. BESTCOMS-BE2000E screen settings are updated only
after communication is opened or the communication settings have been changed.
Open the BE2000E communication port by clicking on
Communications
on the menu bar, hovering the
mouse pointer over
Open Comm Port
, and clicking
RS-232 Port
. Figure 16 illustrates the menu selections
for opening the BE2000E communication port.
Figure 16. Communications Port Menu Selection
When RS-232 Port is selected, the Password dialog box of Figure 17 appears and prompts you to enter a
password. Each BE2000E is delivered with "OEM" as the default password. See the
Password Protection
sub-section for information about changing the password.
Figure 17. Password Dialog Box
After the correct password is entered, the
Communication Initialization
screen of Figure 18 is displayed.
Select Com 1, Com 2, Com 3, or Com 4 as the active communication port on your PC and click the
Initialize
button. BESTCOMS-BE2000E initializes communication by obtaining the configuration settings
from the BE2000E.
Figure 18. Communication Initialization Screen
BE2000E
BESTCOMS
™
Software
Summary of Contents for BE2000E
Page 2: ......
Page 8: ...vi 9287500995 Rev B Contents BE2000E ...
Page 10: ...2 9287500995 Rev B General Information BE2000E ...
Page 28: ...20 9287500995 Rev B Figure 4 BE2000E Dimensions Installation BE2000E ...
Page 29: ...9287500995 Rev B 21 Figure 5 Cutout and Drilling Dimensions BE2000E Installation ...
Page 40: ...32 9287500995 Rev B Installation BE2000E ...
Page 68: ...60 9287500995 Rev B BESTCOMS Software BE2000E ...
Page 74: ...66 9287500995 Rev B Maintenance and Troubleshooting BE2000E ...
Page 80: ...72 9287500995 Rev B Revision History BE1 11f ...
Page 81: ......