Integral means that the BE2000E output is proportional to the amount of time that a change is observed.
Integral action eliminates offset. Derivative means that the BE2000E output is proportional to the required
rate of excitation change. Derivative action avoids excitation overshoot.
BESTCOMS-BE2000E automatically calculates PID values after the user selects the generator
frequency, generator time constant (T'do), and exciter time constant (Texc). With BESTCOMS-BE2000E
software, the user may generate new PID numbers, add to a PID list file, and update the AVR gain
settings.
The PID window (Figure 36) is accessed by clicking the
PID
button. The
PID
button can be clicked only
when the Stability Range setting of the
Control Gain
screen is set at a value of 21. (A setting of 21
enables the entry of custom stability settings through the PID window.) Then, when a field of the
Control
Gain
screen is changed or selected, the
PID
button changes from gray to yellow and the button can be
clicked to view the PID window. After the PID numbers are modified, calculated, and updated, the PID
window is closed by clicking the
Update Setting Screen
button. The modified PID values are then shown
on the
Control Gain
screen.
Figure 36. PID Window
PID Calculation Based on Input Values
The available range for the exciter time constant depends on the value entered for the generator time
constant. (The default value for the exciter time constant is the generator time constant divided by 6.) The
generator time constant value selected must be in the range of 1.00 to 15.00 seconds and in 0.05
increments. When the generator time constant value is 1.00, the available exciter time constant range is
0.03 to 0.50 in 0.01 second increments. When the generator time constant value is 15.00, the available
exciter time constant range is 0.30 to 3.00 in 0.01 second increments.
For example, when T'do is set at 2.0 seconds, Texc is 0.33. After specifying the input values, a set of PID
parameters (output data) is generated automatically. If T'do is set at 5.00 seconds, then Texc is 0.83
seconds. The calculated KP is 155.47, KI is 138.72, KD is 48, and Kg is 1.
PID parameters can be directly removed from, added to, or modified in the PID List Data. PID parameters
may also be saved into a file (pidlist.dat).
BE2000E
BESTCOMS
™
Software
Summary of Contents for BE2000E
Page 2: ......
Page 8: ...vi 9287500995 Rev B Contents BE2000E ...
Page 10: ...2 9287500995 Rev B General Information BE2000E ...
Page 28: ...20 9287500995 Rev B Figure 4 BE2000E Dimensions Installation BE2000E ...
Page 29: ...9287500995 Rev B 21 Figure 5 Cutout and Drilling Dimensions BE2000E Installation ...
Page 40: ...32 9287500995 Rev B Installation BE2000E ...
Page 68: ...60 9287500995 Rev B BESTCOMS Software BE2000E ...
Page 74: ...66 9287500995 Rev B Maintenance and Troubleshooting BE2000E ...
Page 80: ...72 9287500995 Rev B Revision History BE1 11f ...
Page 81: ......