BE1-25 Installation
4-7
CONNECTIONS
Incorrect wiring may result in damage to the relay. Be sure to check the model and Style Number against
the options listed in the Style Number identification chart, Figure 1-6, before connecting and energizing a
particular relay.
NOTE
Be sure the relay case is hard-wired to earth ground with no smaller than 12 AWG copper
wire attached to the ground terminal on the rear of the relay case. When the relay is
configured in a system with other protective devices, it is recommended to use a separate
lead to the ground bus from each relay.
Except as noted above, connections should be made with minimum wire size of 14 AWG. Typical internal
connections are shown in Figure 4-7. Typical external connections are shown in Figures 4-8 through 4-
11. Be sure to use the correct input power for the power supply specified.