YOU:
0**
Acknowledge request is not used
1**
Acknowledge request is used
**
Next
Default: 1 (enabled)
Call Progress (Dial Tone Enable)
This setting enables or disables the feature where the B1290 monitors the
audio activity on the phone line when it places a call. If enabled, Call Prog-
ress will cause the B1290 to look for dial tone before dialing, watch for a
busy signal on the called line and then wait until the called party speaks be-
fore the alarm announcement begins. Without Call Progress enabled, the
B1290 will perform the dial-out operation and speak regardless of the sig-
nals encountered on the phone line.
Do not use the Answer command immediately following a Dial command
in the directories when Call Progress is enabled. This is the equivalent of
two Answer commands and may result in unreliable operation.
B1290: Dial Tone is …
YOU:
0**
Call Progress is not used
1**
Call Progress is used
**
Next
Default: 1 (enabled)
Program Code 7
ÞÞ
: Expanders
When Program Code 7 is entered, the B1290 gives you the following param-
eters.
Number of Expanders
Increase the capacity of a basic B1290 by adding up to 7 expanders, each
with an additional 8 alarm inputs and 4 relay outputs.
B1290: Expander Number is . . .
YOU:
X**
Expanders ( x = 0 to 7 )
**
Next
Default: 0
42