22 

3)   Part number for 1-phase supply different to part number for 3-phase supply

 

 

Model ODP-xxxxx-zz

   1) 

34055 34075 34110 34150 

** 

Motor output rating – industrial 150% o/l 

kW 

5.5 

7.5 

11.0 

15.0 

 

Model 

ODP-xxxxx-USA 

34075 

34100 

34150 

34200 ** 

Motor output rating – industrial 150% o/l 

HP 

7.5 

10 

15 

20 

 

Supply voltage / phases 

V±10% 

380-480 / 1Ø (with 50% derating) or 3Ø 

Supply fuse or MCB (type B)      

2)

 

32 32 50 50 

Output voltage / phases 

0-480 / 3Ø 

Output Amps – industrial 150% overload 

14 

18 

25  (* 24) 

30 

Motor cable size, Copper 75 

o

C mm

2.5 2.5  4  6 

Max motor cable length 

100 

Min brake resistor 

 22 

 
 
 

Model ODP-xxxxx-zz

   1) 

35075 35110 35150 

** 

Motor output rating – industrial 150% o/l 

kW 

7.5 

11.0 

15.0 

 

Model 

ODP-xxxxx-USA 

35100 

35150 

35200 ** 

Motor output rating – industrial 150% o/l 

HP 

10 

15 

20 

 

Supply voltage / phases 

V±10% 

440-575 / 1Ø (with 50% derating) or 3Ø 

Supply fuse or MCB (type B)      

2)

 

32 32 50 

Output voltage / phases 

0-575V / 3Ø 

Output Amps – industrial 150% overload 

14 

18 

24 

Motor cable size, Copper 75 

o

C mm

2.5 4 

Max motor cable length 

100 

Min brake resistor 

 22 

 

* Maximum rating for UL applications 

 

** Models not UL listed 

 
 

SIZE 4 (INTEGRAL RFI FILTER, LINE CHOKE & BRAKING TRANSISTOR) 

 

Model ODP-xxxxx-zz

   1)

 

42075 42110 42150 42185 

Motor output rating – industrial 150% o/l 

KW 

7.5 

11 

15 

18.5 

 

Model 

ODP-xxxxx-USA 

42100 

42150 

42200 

42250 

Motor output rating – industrial 150% o/l 

HP 

10 

15 

20 

25 

 

Supply voltage / phases 

V±10% 

220-240 / 1Ø(with 50% derating) or 3Ø 

Supply fuse or MCB (type B)      2) 

80 

80-100 

100 

125 

Output voltage / phases 

0-240 / 3Ø 

Output Amps – industrial 150% overload 

39 

46 

61 

72 

Motor cable size, Copper 75 

o

C mm

10 10 16 16 

Max motor cable length 

100 

Min brake resistor 

 12 

 

Model ODP-xxxxx-zz

   1)

 

44185 44220 44300 44370 

Motor output rating – industrial 150% o/l 

KW 

18.5 

22 

30 

37 

 

Model 

ODP-xxxxx-USA 

44250 

44300 

44400 

44500 

Motor output rating – industrial 150% o/l 

HP 

25 

30 

40 

50 

 

Supply voltage / phases 

V±10% 

380-480 / 1Ø (with 50% derating) or 3Ø 

Supply fuse or MCB (type B)      2) 

80 

80-100 

100 

125 

Output voltage / phases 

0-480 / 3Ø 

Output Amps – industrial 150% overload 

39 

46 

61 

72 

Motor cable size, Copper 75 

o

C mm

10 10 16 16 

Max motor cable length 

100 

Min brake resistor 

 12 

 
 

SIZE 5 (INTEGRAL RFI FILTER, LINE CHOKE & BRAKING TRANSISTOR)

 

 

Model ODP-xxxxx-zz

   1)

 

52220 52300 52370 52450 

Motor output rating – industrial 150% o/l 

kW 

22 

30 

37 

45 

 

Model 

ODP-xxxxx-USA 

52300 

52400 

52500 

52600 

Motor output rating – industrial 150% o/l 

HP 

30 

40 

50 

60 

 

Supply voltage / phases 

V±10% 

220-240 / 1Ø (with 50% derating) or 3Ø 

Supply fuse or MCB (type B)      

2)

 A 

160 200 

250-300 

250-300 

Output voltage / phases 

0-240 / 3Ø 

Output Amps – industrial 150% overload 

90 

110 

150 

180 

Motor cable size, Copper 75 

o

C mm

25 35 55 70 

Max motor cable length 

100 

Min brake resistor 

 3 

 
1)   “-zz” in the part number refers to the country variation 

CONTENTS 
 

 

 

         

 

 

   

 

        Page 

 

1. General

 

4

 

1.1  Important safety information                                                                                          4 
1.2  Electromagnetic Compatibility (EMC) 

 

2. Mechanical 

Installation

              

5

 

2.1 General 

2.2  Mechanical dimensions and mounting 

2.3 Enclosure 

mounting 

 

3. Electrical 

Installation 

7

 

3.1 Safety 

3.2 Precautions 

3.3  Drive and motor connection  

3.4 Control 

terminal 

connections 

 

4. Operation 

10

 

4.1  Managing the keypad 

10 

4.2 Easy 

startup 

10 

 

5. Configuration 

11

 

5.1 Basic 

parameters 

11 

5.2 Extended 

parameters 

12 

5.3  User Feedback control  

15 

5.4  High performance Motor control 

15 

5.5  Digital input configuration – terminal mode 

16 

5.6  Digital input configuration – keypad mode 

17 

5.7  Digital input configuration – User PID mode 

17 

5.8  Digital input configuration – Modbus control mode (Optional) 

18 

5.9 Real-time 

monitoring 

parameters 

18 

 

6. Troubleshooting 

19

 

6.1  Fault finding chart 

19 

6.2 Fault 

messages 

19 

6.3  Auto-tune trouble shooting 

20 

  

7.   Technical data 

20 

7.1 User 

interface 

20 

7.2  Power stage protection 

20 

7.3 Environmental 

20 

7.4 Rating 

tables 

21 

 

 

All rights reserved. No part of this User Guide may be reproduced or transmitted in any form 
or by any means, electrical or mechanical including photocopying, recording or by any 
information storage or retrieval system without permission in writing from the publisher.  

Copyright Invertek Drives Ltd 

©

 

2006 

 

The manufacturer accepts no liability for any consequences resulting from inappropriate, 
negligent or incorrect installation, or adjustment of the optional operating parameters of the 
drive or from mismatching of the drive to the motor. 

 

The contents of this User Guide are believed to be correct at the time of printing. In the 
interest of a commitment to a policy of continuous improvement, the manufacturer reserves 
the right to change the specification of the product or its performance or the contents of the 
User Guide without notice. 

All Invertek drives products carry a 2-year warranty, valid from the data of manufacture. This 
data is clearly visible on the rating label. 

Summary of Contents for OPTIDRIVE PLUS 3 GV

Page 1: ......

Page 2: ...ve VTC statischer Frequenzumrichter zur Drehzahlregelung von Asynchronmotoren nach den folgenden harmonisierten Produktnormen entwickelt und gebaut wird EN 61800 5 1 Elektrische Leistungsantriebssyste...

Page 3: ...0 7 Technical data 20 7 1 User interface 20 7 2 Power stage protection 20 7 3 Environmental 20 7 4 Rating tables 21 All rights reserved No part of this User Guide may be reproduced or transmitted in a...

Page 4: ...Within the European Union all machinery in which this product is used must comply with Directive 89 392 EEC Safety of Machinery In particular the electrical equipment should comply with EN60204 1 1 2...

Page 5: ...t be less than 95 non condensing Optidrives can be installed side by side with their heatsink flanges touching This gives adequate ventilation space between them If the Optidrive is to be installed ab...

Page 6: ...mplemented The filter must be serviced cleaned appropriately High moisture salt or chemical content environments should use a suitably sealed non vented enclosure Non Vented Metallic Enclosure Dimensi...

Page 7: ...in the mains supply to the drive Do not install any type of automatic switchgear between the drive and the motor Wherever control cabling is close to power cabling maintain a minimum separation of 100...

Page 8: ...ormally selected when installing the motor by selecting either STAR or DELTA connection STAR always gives the higher of the two voltage ratings Typical ratings are 400 230 690 400 DELTA Connection STA...

Page 9: ...output 0 24V 10mA max Terminal 4 2 nd analog input 11 bit 0 05 0 10V 0 20mA 4 20mA Digital input 3 positive logic Logic 1 when Vin 8V DC Terminal 5 24V 100mA reference output for use with potentiomete...

Page 10: ...nsure that extended menu access is enabled then press NAVIGATE simultaneously pressing and releasing the UP key until the required parameter group is displayed To reset factory default parameters pres...

Page 11: ...celeration ramp without over voltage trip P1 08 Motor rated current 20 to 100 of drive rated current Drive rating Set to motor rated current from nameplate Amps P1 09 Motor rated frequency 25 to 2 000...

Page 12: ...ed 2x rated motor torque motor rated output torque 1 5x rated power of the drive or 2x rated motor current P2 12 h Digital output control high limit Speed 0 100 100 max speed Torque 0 200 100 rated to...

Page 13: ...ntrols drive to start or stop The start and stop button will not work in this case P2 20 Standby mode 0 Disable 1 60s 0 If P2 20 0 drive enters standby mode disables output if minimum speed P1 02 is m...

Page 14: ...20mA 0 20mA 0 24V Determines the format of the 2nd analog input Selecting 0 24V sets up the input as a digital input P2 34 2nd analog input scaling 0 500 0 100 0 Scales the 2nd analog input by the fa...

Page 15: ...rol P4 01 Control mode 0 Speed control vector 1 Torque control vector 2 Speed control V F 2 Whenever changing control mode ensure that an Auto tune P4 02 is always carried out for best motor performan...

Page 16: ...Disable C Run Reverse External trip input O Trip C OK Bipolar analog input 11 O Stop Disable C Run Enable O Bipolar analog input C Preset speed 1 External trip input O Trip C OK Bipolar analog input 1...

Page 17: ...reset speed 4 19 O Stop Disable C Run Enable O Digital speed ref C 2 nd analog input No effect 20 21 O Stop Disable C Run Enable 2 nd digital output Drive healthy 24V O Digital speed ref C Preset spee...

Page 18: ...ess to internal drive read only parameters for monitoring purposes Par Description Display range Explanation P0 01 Bipolar analog input value 100 100 100 max input voltage P0 02 2nd analog input value...

Page 19: ...hort circuit on output If wiring correct contact your supplier I t trP Drive overload trip occurring when the drive has been delivering 100 rated current set in P1 08 for a period of time The display...

Page 20: ...Range settings 0 10V 4 20mA 0 20mA Max input voltage 30V DC Input impedance 70 kOhm Digital inputs Positive logic only Sampling interval 8ms sampling time terminals 2 3 4 Logic 1 input voltage range...

Page 21: ...0 Output voltage phases V 0 480 3 Output Amps industrial 150 overload A 2 2 4 1 5 8 9 5 Motor cable size Copper 75 o C mm 2 1 0 1 5 Max motor cable length m 50 100 100 100 Min brake resistor 47 47 47...

Page 22: ...42100 42150 42200 42250 Motor output rating industrial 150 o l HP 10 15 20 25 Supply voltage phases V 10 220 240 1 with 50 derating or 3 Supply fuse or MCB type B 2 A 80 80 100 100 125 Output voltage...

Page 23: ...ength m 100 Min brake resistor 3 Model ODP xxxxx zz 1 64110 64132 64160 Motor output rating industrial 150 o l kW 110 132 160 Model ODP xxxxx USA 64150 64175 64210 Motor output rating industrial 150 o...

Reviews: