5.5  Digital input configuration – terminal mode (P1-12 = 0) 

 

P2-01 

Digi input 1 function 

Digi input 2 function 

Digi input 3 function 

Analog input function 

O : Stop (Disable) 
C : Run (Enable)  

O : Bipolar analog input  
C : Preset speed 1, 2 

O : Preset speed 1  
C : Preset speed 2 

Bipolar analog input 

O : Stop (Disable) 
C : Run (Enable) 

O : Preset speed 1 
C : Preset speed 2 

O : Preset speed 1, 2  
C : Preset speed 3 

O : Preset speed 1,2,3  
C : Preset speed 4 

Digi input 2 

Digi input 3 

Analog input 

Preset value 

Open 

Open 

Open 

Preset speed 1 

Closed 

Open 

Open 

Preset speed 2 

Open 

Closed 

Open 

Preset speed 3 

Closed 

Closed 

Open 

Preset speed 4 

Open 

Open 

Closed 

Preset speed 5 

Closed 

Open 

Closed 

Preset speed 6 

Open 

Closed 

Closed 

Preset speed 7 

O : Stop (Disable) 
C : Run (Enable) 

Closed 

Closed 

Closed 

Preset speed 8 

O : Stop (Disable) 
C : Run (Enable) 

O : Forward 
C : Reverse 

O : Bipolar analog input  
C : Preset speed 1 

Bipolar analog input 

O : Stop (Disable) 
C : Run (Enable) 

O : Forward 
C : Reverse 

2

nd

 Analog Input  

(eg varies torque limit) 

Bipolar analog input 

Digi input 3 

Analog input 

Preset value 

Open 

Open 

Preset speed 1 

Closed 

Open 

Preset speed 2 

Open 

Closed 

Preset speed 3 

O : Stop (Disable) 
C : Run (Enable) 

O : Forward 
C : Reverse 

Closed 

Closed 

Preset speed 4 

    6  

2)

 

O : Stop (Disable) 
C : Run (Enable) 

O : Forward 
C : Reverse 

External trip input : 
O : Trip     C : OK 

Bipolar analog input 

O : Stop (Disable) 
C : Run Forward  

O : Stop (Disable) 
C : Run Reverse 

O : Bipolar analog input  
C : Preset speed 1 

Bipolar analog input 

    8  

2)

 

O : Stop (Disable) 
C : Run Forward  

O : Stop (Disable) 
C : Run Reverse 

O : Preset speed 1 
C : Bipolar analog input 

Bipolar analog input 

Digi input 3 

Analog input 

Preset value 

Open 

Open 

Preset speed 1 

Closed 

Open 

Preset speed 2 

Open 

Closed 

Preset speed 3 

O : Stop (Disable) 
C : Run Forward  

O : Stop (Disable) 
C : Run Reverse 

Closed 

Closed 

Preset speed 4 

   10  

2)

 

O : Stop (Disable) 
C : Run Forward  

O : Stop (Disable) 
C : Run Reverse 

External trip input : 
O : Trip     C : OK 

Bipolar analog input 

11 

O : Stop (Disable) 
C : Run (Enable) 

O : Bipolar analog input  
C : Preset speed 1 

External trip input : 
O : Trip     C : OK 

Bipolar analog input 

   12  

2)

 

O : Stop (Disable) 
C : Run (Enable) 

O : Preset speed 1 
C : Bipolar analog input 

External trip input : 
O : Trip     C : OK 

Bipolar analog input 

13 

Normally open (NO) 
Momentarily close to run 

Normally closed (NC) 
Momentarily open to stop 

O : Bipolar analog input  
C : Preset speed 1 

Bipolar analog input 

14 

Normally open (NO) 
Momentarily close to run 
forward 

Normally closed (NC) 
Momentarily open to stop 

Normally open (NO) 
Momentarily close to run 
reverse 

Bipolar analog input 

15 

O : Stop (Disable) 
C : Run (Enable) 

O : Forward 
C : Reverse 

O : Decel ramp 1 
C : Decel ramp 2 

Bipolar analog input 

16 

O : Stop (Disable) 
C : Run (Enable) 

O : Forward 
C : Reverse 

O : Decel ramp 1 
C : Decel ramp 2 

O : Preset speed 1  
C : Preset speed 2 

17 

Normally open (NO) 
Momentarily close to run 
forward 

Normally closed (NC) 
Momentarily open to stop 

Normally open (NO) 
Momentarily close to run 
reverse 

O : Preset speed 1 
C : Keypad mode 

Digi input 2 

Digi input 3 

Preset value 

Open 

Open 

Preset speed 1 

Closed 

Open 

Preset speed 2 

Open 

Closed 

Preset speed 3 

18 

O : Stop (Disable) 
C : Run (Enable) 

Closed 

Closed 

Preset speed 4 

O : Terminal mode 
C : Keypad mode 

19 

O : Stop (Disable) 
C : Run (Enable) 

O : Bipolar analog input 
C : 2

nd

 analog input 

2

nd

 analog input 

Bipolar analog input 

   20  

1)

 

O : Stop (Disable) 
C : Run (Enable) 

2

nd

 digital output : 

Drive healthy = +24V 

O : Bipolar analog input  
C : Preset speed1 

Bipolar analog input 

   21  

1)

 

O : Stop (Disable) 
C : Run (Enable) 

2

nd

 digital output : 

Drive healthy = +24V 

O : Forward 
C : Reverse 

Bipolar analog input 

   22  

1)

 

O : Stop (Disable) 
C : Run (Enable) 

2

nd

 digital output : 

Drive healthy = +24V 

External trip input : 
O : Trip     C : OK 

Bipolar analog input 

 

Notes : 

1) 

When P2-01 = 20, 21 or 22, the 2

nd

 digital input is configured as an output, which o24V 

when the drive is healthy, otherwise 0V 

2) 

When connecting a motor thermistor, connect between terminals 1 & 4, set P2-01 = 6, 10, 11, 
12 or 22 (Uses external trip input) 

3.4  Control Terminal Connections 

 

The User Control terminals are available via an 11-way pluggable connector.  All 
terminals are galvanically isolated, allowing direct connection to other equipment. 

 
Do not connect mains supply voltages to any terminals other than the User 
relay output. Permanent damage will otherwise result. 
 

All other inputs will withstand up to 30V dc without damage.   
 
The functionality of the inputs and outputs is user configurable. All operating modes are 
set up via the parameter set. 
 
Up to 100mA can be sourced from the User +24V output and up to 20mA from the 
analog output. 

 

The control terminals are defined as follows : 

 
 
 
 

 
 

 

Terminal 1: 

+24V, 100mA user output.  

Terminal 2: 

Digital input 1, positive logic.  “Logic 1” when Vin > 8V DC 

Terminal 3: 

Digital input 2, positive logic.  “Logic 1” when Vin > 8V DC 
2

nd

 digital output : 0 / 24V, 10mA max 

 

 

Terminal 4: 

2

nd

 analog input, 11-bit (0.05%).  0..10V,  0..20mA,  4..20mA. 

Digital input 3, positive logic.  “Logic 1” when Vin > 8V DC. 

 

 

Terminal 5: 

+24V, 100mA reference output (for use with potentiometer). 

Terminal 6: 

Bipolar analog input, +/-12-bit (0.025%).   
Configurable for :  0..24V,  0..10V,  -10V...10V,  -24V…24V 

 

 

Terminal 7: 

0V (User GND).  Connected to terminal 9 

Terminal 8: 

Analog output, 8-bit (0.25%). 0..10V,  4..20mA. 
Digital output : 0 / 24V, 20mA max 

 

 

Terminal 9: 

0V (User GND).  Connected to terminal 7 

Terminal 10:

 

User relay output. Potential free contacts. 30Vdc 5A, 250Vac 6A 

Terminal 11: 

User relay output. Potential free contacts. 30Vdc 5A, 250Vac 6A 

 

Key control terminal information : 

 

 

Maximum input voltage on any terminal 30V dc 

 

All outputs short circuit proof 

 

Recommended potentiometer resistance : 10k Ohm 

 

Digital input response time < 8ms 

 

Bipolar analog input response time < 16ms.   Resolution  +/-12 bit  (0.025%) 

 

Second analog input response time < 16ms.   Resolution  +11 bit  (0.05%) 

 

Analog / Digital output response time < 16ms.  Resolution  8 bit  (0.25%) 

2 3 4 5 6 7 8 9 10 11

Summary of Contents for OPTIDRIVE PLUS 3 GV

Page 1: ......

Page 2: ...ve VTC statischer Frequenzumrichter zur Drehzahlregelung von Asynchronmotoren nach den folgenden harmonisierten Produktnormen entwickelt und gebaut wird EN 61800 5 1 Elektrische Leistungsantriebssyste...

Page 3: ...0 7 Technical data 20 7 1 User interface 20 7 2 Power stage protection 20 7 3 Environmental 20 7 4 Rating tables 21 All rights reserved No part of this User Guide may be reproduced or transmitted in a...

Page 4: ...Within the European Union all machinery in which this product is used must comply with Directive 89 392 EEC Safety of Machinery In particular the electrical equipment should comply with EN60204 1 1 2...

Page 5: ...t be less than 95 non condensing Optidrives can be installed side by side with their heatsink flanges touching This gives adequate ventilation space between them If the Optidrive is to be installed ab...

Page 6: ...mplemented The filter must be serviced cleaned appropriately High moisture salt or chemical content environments should use a suitably sealed non vented enclosure Non Vented Metallic Enclosure Dimensi...

Page 7: ...in the mains supply to the drive Do not install any type of automatic switchgear between the drive and the motor Wherever control cabling is close to power cabling maintain a minimum separation of 100...

Page 8: ...ormally selected when installing the motor by selecting either STAR or DELTA connection STAR always gives the higher of the two voltage ratings Typical ratings are 400 230 690 400 DELTA Connection STA...

Page 9: ...output 0 24V 10mA max Terminal 4 2 nd analog input 11 bit 0 05 0 10V 0 20mA 4 20mA Digital input 3 positive logic Logic 1 when Vin 8V DC Terminal 5 24V 100mA reference output for use with potentiomete...

Page 10: ...nsure that extended menu access is enabled then press NAVIGATE simultaneously pressing and releasing the UP key until the required parameter group is displayed To reset factory default parameters pres...

Page 11: ...celeration ramp without over voltage trip P1 08 Motor rated current 20 to 100 of drive rated current Drive rating Set to motor rated current from nameplate Amps P1 09 Motor rated frequency 25 to 2 000...

Page 12: ...ed 2x rated motor torque motor rated output torque 1 5x rated power of the drive or 2x rated motor current P2 12 h Digital output control high limit Speed 0 100 100 max speed Torque 0 200 100 rated to...

Page 13: ...ntrols drive to start or stop The start and stop button will not work in this case P2 20 Standby mode 0 Disable 1 60s 0 If P2 20 0 drive enters standby mode disables output if minimum speed P1 02 is m...

Page 14: ...20mA 0 20mA 0 24V Determines the format of the 2nd analog input Selecting 0 24V sets up the input as a digital input P2 34 2nd analog input scaling 0 500 0 100 0 Scales the 2nd analog input by the fa...

Page 15: ...rol P4 01 Control mode 0 Speed control vector 1 Torque control vector 2 Speed control V F 2 Whenever changing control mode ensure that an Auto tune P4 02 is always carried out for best motor performan...

Page 16: ...Disable C Run Reverse External trip input O Trip C OK Bipolar analog input 11 O Stop Disable C Run Enable O Bipolar analog input C Preset speed 1 External trip input O Trip C OK Bipolar analog input 1...

Page 17: ...reset speed 4 19 O Stop Disable C Run Enable O Digital speed ref C 2 nd analog input No effect 20 21 O Stop Disable C Run Enable 2 nd digital output Drive healthy 24V O Digital speed ref C Preset spee...

Page 18: ...ess to internal drive read only parameters for monitoring purposes Par Description Display range Explanation P0 01 Bipolar analog input value 100 100 100 max input voltage P0 02 2nd analog input value...

Page 19: ...hort circuit on output If wiring correct contact your supplier I t trP Drive overload trip occurring when the drive has been delivering 100 rated current set in P1 08 for a period of time The display...

Page 20: ...Range settings 0 10V 4 20mA 0 20mA Max input voltage 30V DC Input impedance 70 kOhm Digital inputs Positive logic only Sampling interval 8ms sampling time terminals 2 3 4 Logic 1 input voltage range...

Page 21: ...0 Output voltage phases V 0 480 3 Output Amps industrial 150 overload A 2 2 4 1 5 8 9 5 Motor cable size Copper 75 o C mm 2 1 0 1 5 Max motor cable length m 50 100 100 100 Min brake resistor 47 47 47...

Page 22: ...42100 42150 42200 42250 Motor output rating industrial 150 o l HP 10 15 20 25 Supply voltage phases V 10 220 240 1 with 50 derating or 3 Supply fuse or MCB type B 2 A 80 80 100 100 125 Output voltage...

Page 23: ...ength m 100 Min brake resistor 3 Model ODP xxxxx zz 1 64110 64132 64160 Motor output rating industrial 150 o l kW 110 132 160 Model ODP xxxxx USA 64150 64175 64210 Motor output rating industrial 150 o...

Reviews: