14 

P2-26 

Modbus RTU 
baudrate option 

9.6kbps to 115.2kbps 

115.2 

Modbus RTU communication 
network baudrate. Only available if 
optional Modbus plug-in installed 

P2-27 

Drive communication 
address 

0: Disable   1..63 

Distinct drive address used for all 
drive serial communications. 

P2-28 

Master / Slave mode 
select 

0: Slave mode 
1: Master mode 

When in Master mode, the drive 
transmits its operational status via 
the serial data link. Used to control 
slave drives via the serial link.  
P2-27 must be 1 for Master mode. 

P2-29 

Digital speed  
reference preset 
scaling factor 

0…500%, steps of 0.1%  100.0% 

The digital speed reference input 
to the drive is scaled by this factor 
when P2-35 = 1. Operates on 
references originating from the 
serial data link.  
Can be used as an electronic 
gearbox for Master / Slave 
applications. 

P2-30 

Bipolar analog input 
format 

0..24V, 0..10V, -10..10V, 
-24..24V 

0..24V 

Configures the analog input format 
to match that of the reference 
signal connected to terminal 6 

P2-31 

Bipolar analog input 
scaling 

0...500.0% 100.0% 

Scales the analog input by this 
factor. Set to 200% to give full 
speed range control with 0..5V 
input (when P2-30 = 0..10V) 

P2-32 

Bipolar analog input 
offset 

-500.0%...500.0% 0.0% 

Sets the offset from zero at which 
speed starts to ramp up.  
Value is “%” of the full scale input 
voltage. 

P2-33 

2

nd

 analog input 

format 

0 / 24V (digital input) 
0..10V, 
4..20mA,  0..20mA 

0 / 24V 

Determines the format of the 2

nd

 

analog input. 
Selecting 0 / 24V sets up the input 
as a digital input. 

P2-34 

2

nd

 analog input 

scaling 

0...500.0% 100.0% 

Scales the 2

nd

 analog input by the 

factor set in this parameter.  

P2-35 

Digital speed 
reference scaling 
control 

0: Disabled (no scaling) 
1: Scaling set by preset    
     value in P2-29 
2: Slave speed scaled 
     by preset value in    
     P2-29, then bipolar  
     analog input added  
     as offset 
3: Slave speed scaled    
     by preset value in      
     P2-29 

and

 by bipolar   

     analog input 

Only active in keypad control mode 

and usually used in a Master/Slave 
network application. 

When P2-35 = 1, actual speed =  
          Digital speed * P2-29. 

 

When P2-35 = 2, actual speed =  
   (Digital speed x P2-29) +  
                      bipolar analog input 
Max analog input is equal to P1-01 

 

When P2-35 = 3, actual speed =  
   (Digital speed x P2-29) x  
                      bipolar analog input 
Analog input scales 0% … 200% 

P2-36  Analog output format 

0..10V 
4..20mA 
10..0V 
20..4mA 

0..10V 

Determines the analog output 
format.  
Min load impedance in voltage 
mode 1k Ohm.  
Max load impedance in current 
mode 1k Ohm. 

P2-37 

Extended menu 
access code define 

0…9999 101 

Defines the extended menu 
access code used in P1-14. 

P2-38 Parameter 

Lock 

0: Unlocked 
1: Locked 

When locked, all parameter 
changes are prevented. 

P2-39  Hours run clock 

0 to 99999 hours 

Read 
only 

Indicates the number of hours the 
drive has been running since new.  

P2-40  Drive type / rating 

“     0.37“,   “0   230” : 

3

GV

 230V 0.37kW 

“HP   20”,   “1   460“ : 
         VTC, 460V 20HP 

Read 
only 

Indicates drive power rating, type 
code and voltage rating.   
Drive type code indicates 3GV (0), 
VTC (1) or other drive type 

11 

5. 

Drive Configuration  

 

5.1  Group 1 : Basic Parameters 

 

Par. Description 

Range 

Default Explanation 

P1-01 

Max speed limit 

P1-02 to P1-09 x 5 
(up to 2 000Hz max) 

50 Hz 

Sets the maximum speed limit. 
Display of Hz or rpm dependent on 
P1-10.  Maximum speed limit 
dependent on switching frequency: 
Max Limit = P2-24 / 16. 

P1-02 

Min speed limit 

0 to P1-01 

0 Hz 

Minimum speed limit. Hz or rpm 
display depending on P1-10. 

P1-03 

Accel ramp time 

0 to 3 000s 

5.0s 

Time to ramp from 0 to rated 
frequency (P1-09) 

P1-04 

Decel ramp time 

0 to 3 000s 

5.0s 

Time to ramp from rated frequency 
(P1-09) to 0.  When P1-04 = 0, the 
ramp is varied dynamically to give 
the fastest possible ramp to STOP.  

P1-05 Stop 

mode 

select 

0: Ramp to stop 
1: Coast to stop 
2: Ramp to stop 

If the supply is lost and P1-05 = 0 
then the drive will try to continue 
running by reducing load speed, 
using the load as a generator  
If P1-05 = 2, the drive ramps on 
2nd decel ramp P2-25 to stop. 

P1-06 Energy 

Optimisation 

0: Disable 
1: Enable 

When enabled, automatically 
reduces applied motor voltage on 
light load. Used in V/F mode only. 

P1-07 Motor 

rated 

voltage 

0V, 20V to 250V 
0V, 20V to 500V 
 
0V, 20V to 600V 

230V 
400V 
(460V) 
575V 

Set to motor rated voltage from 
nameplate. When in V/F mode, 
P1-07 = 0 gives faster deceleration 
ramp without over-voltage trip 

P1-08 

Motor rated current 

20% to 100% of drive 
rated current 

Drive 
rating 

Set to motor rated current from 
nameplate (Amps) 

P1-09 

Motor rated 
frequency 

25 to 2 000Hz 

50Hz 
(60Hz) 

Set to motor rated frequency from 
nameplate (Hz). Maximum limit 
dependent on switching frequency:   
Max Limit = P2-24 / 16. 

P1-10 

Motor rated speed 

0 to 60 000rpm 

When 0, drive operates in Hz. 
Upper limit set to 60 x P1-09. 
This value usually can be found in 
the motor nameplate. 

P1-11 

Preset speed 1 

-P1-01  to  P1-01 

50Hz 
(60Hz) 

Sets jog / preset speed at which 
drive runs when preset speed 1 
selected via digital inputs. 
(see also P2-01) 

P1-12 

Terminal / Keypad 
control of drive 

0: Terminal control 
1: Keypad control 
    (Fwd only) 
2: Keypad control 
    (Fwd and Rev) 
3: Enable User PID 
4: Modbus network      
    control (Optional) 

0 : Terminal control 
1 : Uni-direction keypad control.  
2 : Bi-directional keypad control. 
Keypad START button toggles 
between forward and reverse. 
3 : User PID (feedback control) 
active, setup in parameter group 3. 
4 : Drive controlled via integrated 
Modbus RTU interface. Note that 
this is an upgrade option and is not 
available in the standard OD Plus.  

P1-13 

Trip Log 

Last 4 trips stored 

Latest 4 trips stored. Most recent 
trip displayed first. 

P1-14 

Extended Menu 
Access code 

0 to 30 000 

Permits access to extended menu 
when P1-14 = P2-37. Default 
access value = 101. 

 

Notes: 

 

Default parameter values for Horse Power rated drives are shown in brackets 

Summary of Contents for OPTIDRIVE PLUS 3 GV

Page 1: ......

Page 2: ...ve VTC statischer Frequenzumrichter zur Drehzahlregelung von Asynchronmotoren nach den folgenden harmonisierten Produktnormen entwickelt und gebaut wird EN 61800 5 1 Elektrische Leistungsantriebssyste...

Page 3: ...0 7 Technical data 20 7 1 User interface 20 7 2 Power stage protection 20 7 3 Environmental 20 7 4 Rating tables 21 All rights reserved No part of this User Guide may be reproduced or transmitted in a...

Page 4: ...Within the European Union all machinery in which this product is used must comply with Directive 89 392 EEC Safety of Machinery In particular the electrical equipment should comply with EN60204 1 1 2...

Page 5: ...t be less than 95 non condensing Optidrives can be installed side by side with their heatsink flanges touching This gives adequate ventilation space between them If the Optidrive is to be installed ab...

Page 6: ...mplemented The filter must be serviced cleaned appropriately High moisture salt or chemical content environments should use a suitably sealed non vented enclosure Non Vented Metallic Enclosure Dimensi...

Page 7: ...in the mains supply to the drive Do not install any type of automatic switchgear between the drive and the motor Wherever control cabling is close to power cabling maintain a minimum separation of 100...

Page 8: ...ormally selected when installing the motor by selecting either STAR or DELTA connection STAR always gives the higher of the two voltage ratings Typical ratings are 400 230 690 400 DELTA Connection STA...

Page 9: ...output 0 24V 10mA max Terminal 4 2 nd analog input 11 bit 0 05 0 10V 0 20mA 4 20mA Digital input 3 positive logic Logic 1 when Vin 8V DC Terminal 5 24V 100mA reference output for use with potentiomete...

Page 10: ...nsure that extended menu access is enabled then press NAVIGATE simultaneously pressing and releasing the UP key until the required parameter group is displayed To reset factory default parameters pres...

Page 11: ...celeration ramp without over voltage trip P1 08 Motor rated current 20 to 100 of drive rated current Drive rating Set to motor rated current from nameplate Amps P1 09 Motor rated frequency 25 to 2 000...

Page 12: ...ed 2x rated motor torque motor rated output torque 1 5x rated power of the drive or 2x rated motor current P2 12 h Digital output control high limit Speed 0 100 100 max speed Torque 0 200 100 rated to...

Page 13: ...ntrols drive to start or stop The start and stop button will not work in this case P2 20 Standby mode 0 Disable 1 60s 0 If P2 20 0 drive enters standby mode disables output if minimum speed P1 02 is m...

Page 14: ...20mA 0 20mA 0 24V Determines the format of the 2nd analog input Selecting 0 24V sets up the input as a digital input P2 34 2nd analog input scaling 0 500 0 100 0 Scales the 2nd analog input by the fa...

Page 15: ...rol P4 01 Control mode 0 Speed control vector 1 Torque control vector 2 Speed control V F 2 Whenever changing control mode ensure that an Auto tune P4 02 is always carried out for best motor performan...

Page 16: ...Disable C Run Reverse External trip input O Trip C OK Bipolar analog input 11 O Stop Disable C Run Enable O Bipolar analog input C Preset speed 1 External trip input O Trip C OK Bipolar analog input 1...

Page 17: ...reset speed 4 19 O Stop Disable C Run Enable O Digital speed ref C 2 nd analog input No effect 20 21 O Stop Disable C Run Enable 2 nd digital output Drive healthy 24V O Digital speed ref C Preset spee...

Page 18: ...ess to internal drive read only parameters for monitoring purposes Par Description Display range Explanation P0 01 Bipolar analog input value 100 100 100 max input voltage P0 02 2nd analog input value...

Page 19: ...hort circuit on output If wiring correct contact your supplier I t trP Drive overload trip occurring when the drive has been delivering 100 rated current set in P1 08 for a period of time The display...

Page 20: ...Range settings 0 10V 4 20mA 0 20mA Max input voltage 30V DC Input impedance 70 kOhm Digital inputs Positive logic only Sampling interval 8ms sampling time terminals 2 3 4 Logic 1 input voltage range...

Page 21: ...0 Output voltage phases V 0 480 3 Output Amps industrial 150 overload A 2 2 4 1 5 8 9 5 Motor cable size Copper 75 o C mm 2 1 0 1 5 Max motor cable length m 50 100 100 100 Min brake resistor 47 47 47...

Page 22: ...42100 42150 42200 42250 Motor output rating industrial 150 o l HP 10 15 20 25 Supply voltage phases V 10 220 240 1 with 50 derating or 3 Supply fuse or MCB type B 2 A 80 80 100 100 125 Output voltage...

Page 23: ...ength m 100 Min brake resistor 3 Model ODP xxxxx zz 1 64110 64132 64160 Motor output rating industrial 150 o l kW 110 132 160 Model ODP xxxxx USA 64150 64175 64210 Motor output rating industrial 150 o...

Reviews: