Manual 2100-713A
Page
34 of 44
NOTE:
Screenshots shown in this manual reflect
default settings (when applicable).
The LC6000 controller and TEC-EYE hand-held
diagnostic tool will both be used to set up the Bard air
conditioning system (the TEC-EYE is only used to set up
the wall-mount units). If installing a single MULTI-TEC
wall-mount unit with a PGD stand-alone display or th-
Tune single-unit controller, refer to PGD manual 2100-
734 or th-Tune manual 2100-678 for information on
setting up a PGD or th-Tune for single unit operation.
SYSTEM SET UP
FIGURE 27
TEC-EYE Connection to Unit Control
Modular Connector for TEC-EYE
Hand-Held Diagnostic Tool
Main Menu. The menus permit the user to easily view,
control and configure the unit. See the latest version
of MULTI-TEC Service Manual 2100-712 for more
information on using the TEC-EYE.
The TEC-EYE connects to the wall-mount unit control
board via an RJ11 modular connector as shown in
Figure 27.
When not being used, the TEC-EYE hand-held diagnostic
tool should be stored inside or near the LC6000
controller. Do not let the TEC-EYE leave the shelter.
User
2000
Technician
1313
Engineer
9254
Use UP or DOWN keys and ENTER key to enter password
TABLE 5
LC6000/TEC-EYE Passwords (Defaults)
TEC-EYE Hand-Held Diagnostic Tool
The microprocessor control used in the MULTI-TEC
wall-mount air conditioners allows for complete control
and monitoring through the use of the provided TEC-
EYE hand-held monitor.
The menu driven interface provides users the ability
to scroll through two menu levels: Quick Menu and
FIGURE 28
TEC-EYE (Bard P/N 8301-059) Display and Interface (Status Screen Shown)
ALARM KEY
Allows viewing of active alarms
Silences audible alarms
Resets active alarms
MENU KEY
Allows entry to Main Menu
ESCAPE KEY
Returns to previous menu level
Cancels a changed entry
UP KEY
Steps to next screen in the display menu
Changes (increases) the value of a modifiable field
ENTER KEY
Accepts current value of a modifiable field
Advances cursor
DOWN KEY
Steps back to previous screen in the display menu
Changes (decreases) the value of a modifiable field
ALARM KEY
MENU KEY
ESCAPE KEY
DOWN KEY
UP KEY
ENTER KEY
Summary of Contents for MULTI-TEC W18ABP Series
Page 2: ......
Page 12: ......
Page 18: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369 ...
Page 19: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368 ...
Page 24: ......
Page 63: ......
Page 108: ......
Page 111: ......
Page 123: ......
Page 126: ......