Emergency Off, Emergency Ventilation and Generator Run Connections
The LC6000-200 controller is shipped with emergency off, emergency ventilation and generator run contacts. There
are factory-installed jumpers across terminals #6 and #7 (emergency off), #8 and #9 (emergency ventilation) and
#10 and #11 (generator run). Remove the factory-installed jumpers before making the connections.
FIGURE 17
LC6000-200 Series Connection for Emergency Off, Emergency Ventilation and Generator Run (If Applicable)
5
7
9
17
19
21
25
23
27
29
31
35
33
37
11
13
15
39
43
41
45
47
51
49
53
55
59
57
60
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
1
2
3
4
Generator Run*
Emergency Ventilation*
Emergency Off*
* Normally closed (NC) contacts required.
By default:
Closed = No Alarm
Open = Alarm