LIST OF NECESSARY MATERIALS/TOOLS
Additional hardware and miscellaneous supplies are needed for installation. These items are field supplied and must
be sourced before installation. This list also includes tools needed for installation.
List of Materials/Tools
• Personal protective equipment/safety devices/anti-
static wrist straps
• Supply and return grilles
• Field-fabricated sleeves (if necessary)
• Fasteners sufficient for mounting the units such as
5/16" diameter anchor/lag bolts
• 7/8" diameter washers
• Fasteners appropriate for the shelter wall
construction to attach the controller to the wall
• Commercial grade outdoor silicone sealant
• Miscellaneous hand and power tools and jobsite or
shop materials
• Lifting equipment with the necessary capacity and
rigging to safely move/install the systems
• Electrical supplies
- Various size circuit breakers for the shelter AC
breaker box (see Electrical Specification tables
on pages 16, 17 and 18)
- High-voltage wire of various gauges
(see tables on pages 16, 17 and 18)
-
16 gauge minimum, 14 gauge maximum power
wire to connect controller to shelter power source
-
5-wire, 18 gauge shielded cable for remote
temperature and humidity sensors (2-wire, 18
gauge shielded cable for temperature-only sensors)
- Communication wire: 2-wire, 18 gauge, shielded
with drain
- 18 gauge non-shielded wire for connecting
emergency off, emergency vent and/or generator,
if applicable, to controller
-
CAT 6 Ethernet cable of field-determined length
(for remote communication, if applicable)
-
2 hole grounding lug (to be used with supplied
1/4" bolts and nuts for grounding controller box)
- Miscellaneous electrical supplies including rigid/
flexible conduit and fittings, 2" x 4" junction
boxes (one per temperature/humidity sensor),
wire connectors and supports
FIGURE 1
MULTI-TEC W18-36A/LB Wall-Mount Unit Model Nomenclature
CONTROL MODULES
E – Low Ambient Control
C – Low Ambient Control
and Crank Case Heater
COIL OPTIONS
X
–
Standard
1
–
Phenolic Coated Evaporator
2
–
Phenolic Coated Condenser
3
–
Phenolic Coated Evaporator and
Condenser
4
–
Coated Coils and Condenser Section
5
–
Coated Coils, Inside and
Outside of Unit
P
– PLC Logic Board
E
– PLC with Electric Reheat Dehumidification
W
36
A
B
P
A 10 5 X X X X E
MODEL SERIES
REVISION
A –
Right Hand
L –
Left Hand
PLACEHOLDER
X
for future use
CAPACITY
18
–
1½ Ton
24
–
2 Ton
30
–
2½ Ton
36
–
3 Ton
Having "B" in this position in the
model number disables all economizer
function. Emergency vent will still
operate when "B" is in this position.
KW
VENTILATION OPTIONS
B
–
Blank-off Plate
5 or E
–
Economizer
A
–
230/208/60/1
B
–
230/208/60/3
C
–
460/60/3
D
–
240/220/50/1
VOLTS & PHASE
E
–
240/220/50/3
or 220/200/50/3
F
–
415/380/50/3
Q
–
575/60/3
FILTER OPTIONS
X
–
1" Throwaway (Standard)
W
–
1" Washable
P
–
2" Pleated (MERV 8)
COLOR OPTIONS
X
–
Beige (Standard)
1
–
White
4
–
Buckeye Gray
5
–
Desert Brown
8
–
Dark Bronze
S
–
Stainless Steel
A
–
Aluminum
M
–
2" Pleated (MERV 11)
N
–
2" Pleated (MERV 13)
Summary of Contents for MULTI-TEC W18ABP Series
Page 2: ......
Page 12: ......
Page 18: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369 ...
Page 19: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368 ...
Page 24: ......
Page 63: ......
Page 108: ......
Page 111: ......
Page 123: ......
Page 126: ......