Manual 2100-713A
Page
37 of 44
FIGURE 32
Setting Controller Date and Time
3) Press the UP or DOWN keys to scroll to the
Settings
menu; press ENTER key.
4) Press UP or DOWN keys to scroll to
Date/Time
menu; press ENTER key.
5) Press UP or DOWN keys to scroll to
Date/Time
change
.
6) Press ENTER key to scroll to the desired value
to be changed (see Figure 32).
7) Press UP or DOWN keys to change the value.
8) Press ENTER key to save and to scroll to top of
screen.
9) Press UP or DOWN keys to scroll to
Timezone
(if applicable). Follow steps 6-8 to change
timezone.
10) Press ESCAPE key several times to return to
Main Menu screen.
NOTE:
The LC6000 will sync the time and date
configured to each of the wall-mount units once
communication is established.
DOWN KEY
ALARM KEY
MENU KEY
UP KEY
ENTER KEY
ESCAPE KEY
FIGURE 34
LC6000 Controller Display and Interface (Status Screen Shown)
LC6000 interface key functions are the same as those shown for the TEC-EYE in Figure 28 on page 34.
5. Configure Sensors
The system will need to be configured for the
number of temperature and humidity sensors
installed. The system is shipped with one
combination temperature and humidity sensor.
Additional combination sensors may be purchased
or alternatively, temperature-only sensors may be
purchased instead. The LC is capable of utilizing
five temperature sensors and four humidity sensors.
The system will need to be configured for the
various configurations.
If necessary, the sensors could be calibrated at this
time too. For information on calibrating the sensors
(adjusting the offset), see page 42.
To enable/disable
Zone 1 Indoor Humidity
:
1) Press MENU key to go to the Main Menu
screen.
2) Press UP or DOWN keys and ENTER key to
enter USER password 2000.
3) Press UP or DOWN keys to scroll to
IO Config
;
press ENTER key.
4) Press UP or DOWN keys to scroll to
Z1 Indoor
Hum C4
.
5) Press ENTER key to scroll to
Enable
(see
Figure 33).
6) Press UP or DOWN key to change value to ON
to enable sensor (or change value to OFF to
disable sensor).
FIGURE 33
Enable/Disable Zone 1 Indoor Humidity Sensor
Summary of Contents for MULTI-TEC W18ABP Series
Page 2: ......
Page 12: ......
Page 18: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369 ...
Page 19: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368 ...
Page 24: ......
Page 63: ......
Page 108: ......
Page 111: ......
Page 123: ......
Page 126: ......