Run Test Parameter Descriptions
Econ Stage Time: Amount of time (in seconds)
allowed for damper blade movement in each
direction.
Heat/Cool Stage Time: Amount of time (in seconds)
allowed for each stage of heating or cooling.
FIGURE 8
Restoring Factory Default Settings
FIGURE 7
Executing Run Test
Executing a Run Test
This unit has the ability to perform a run test that will
operate all available unit functions in order to quickly
determine unit operation. Some unit parameters are
adjustable.
To execute a run test:
1. Press MENU key to access the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to
Sys Config
;
press ENTER key.
4. Press UP or DOWN keys to scroll to
Run Test A9
screen.
5. Press ENTER key to scroll to
Enable
parameter
(see Figure 7).
6. Press UP or DOWN key to change value to
Yes
.
7. Press ENTER key to save value.
Reset to Factory Defaults
To reset to factory default settings:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter
ENGINEER password 9254.
3. Press UP or DOWN keys to scroll to
Settings
; press
ENTER key.
4. Press UP or DOWN keys to scroll to
Initialization
;
press ENTER key.
5. Press UP or DOWN keys to scroll to the
Default
Installation
screen.
6. Press ENTER key to scroll to
Wipe retain mem.
(see Figure 8).
7. Press UP or DOWN key to change value to
YES
;
press ENTER key.
8. System will restart with default values.