Manual 2100-669F
Page
7 of 37
FIGURE 3
LC6000 Controller Supply Wiring
Supply Wiring
The LC6000 controller is powered by 120, 208 or 240 volts from the shelter. Field-supplied supply wiring should
be minimum 16 gauge, maximum 14 gauge (see Figure 3). A reliable earth ground must be connected in addition
to any grounding from conduit. Grounding bolts and nuts are included with the controller for this purpose; a 2 hole
grounding lug must be field supplied. Install as shown in Figure 4.
Failing to ground the controller box properly could
result in damage to the equipment.
FIGURE 4
Controller Grounding Posts
A reliable earth ground must be connected in
addition to any grounding from conduit. Attach
earth ground to side of controller box using bolts
and nuts supplied with controller and field-
supplied 2 hole grounding lug.
Failing to ground
the controller box properly could result in damage
to the equipment.