FIGURE 18
Adjust Zone Alarm Configuration
LC to provide remote notification of the event for each
zone.
To change the direction of the remote notification relay
output:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter
USER password 2000.
3. Press UP or DOWN keys to scroll to
IO Config
;
press ENTER key.
4. Press UP or DOWN keys to scroll to
Digital Out
Config C3
.
5. Press ENTER key to scroll to the variable in the
table that intersects
Z1Alm
and
Dir
,
Z2Alm
and
Dir
, or
Z3Alm
and
Dir
(see Figure 14 on page 15).
6. Press UP or DOWN key to change direction.
When the direction is set to NO, the relay output will
be closed when the alarm is active and open when
not active. When the direction is set to NC, the relay
output will be open when alarm is active and closed
when not active.
The zone alarms can be configured to actuate based on
15 alarms communicated from each wall unit. These
items can be selected for each zone.
To select which wall unit alarms actuate zone alarms:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to
Adv Sys
Config
; press ENTER key.
4. Press UP or DOWN keys to scroll to
Zone Alarm
Config B4
,
Zone Alarm Config B5
and
Zone Alarm
Config B6
. The 15 alarms are divided between
these three screens.
5. Press ENTER key to scroll to the variable in the
table that intersects with each alarm and zone
number (see Figure 18).
6. Press UP or DOWN key to change value (N or Y).
If a value of Y is entered, the wall unit alarm will
trigger the zone alarm relay output. If a value of N
is entered, the wall unit alarm will not trigger the
zone alarm relay output.
NOTE:
By default, only 'no temperature sensors' and
high and low pressure actuate the alarms.
NOTE:
Power Loss group is also affected by
communication loss.
NOTE:
If no temperature sensors are detected by the
controller for a given zone, that zone alarm
output will be actuated. This is nonconfigurable.
Humidity Alarm
When the LC detects a high indoor humidity or low
indoor humidity event in a selected zone (through an
analog input from a remote sensor), an alarm will be
generated. Additionally, a relay output will be actuated
from the LC to provide remote notification of the event.
The end user can configure the alarm to be actuated
when the measurement is high, low or both high and low.
To adjust the humidity alarm setpoints:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter
USER password 2000.
3. Press UP or DOWN keys to scroll to
Sys Config
;
press ENTER key.
4. Press UP or DOWN keys to scroll to
Zone 1
,
Zone
2
or
Zone 3
; press ENTER key.
5. Press UP or DOWN keys to scroll to
Alarm
Setpoints A2-10
(Zone 1),
Alarm Setpoints A3-10
(Zone 2) or
Alarm Setpoints A4-10
(Zone 3
)
.