Menu Screens and Password Levels
A
System Config
General: User (2000)
Zone 1: User (2000)
Zone 2: User (2000)
Zone 3: User (2000)
B
Adv Sys Config: Technician (1313)
C
I-O Config: Technician (1313)
D
On/Off: User (2000)
E
Alarm Logs: User (2000)
F
Settings
Date/Time: Technician (1313)
Language: User (2000)
Network Config: Technician (1313)
Serial Ports: Technician (1313)
Initialization
Clear Logs: User (2000)
System Default: Engineer (9254)
Restart: User (2000)
Parameter Config: Engineer (9254)
Alarm Export: User (2000)
G
Logout: Used to log out of the current password level.
Entering back into the menu requires a password.
Additional Programming
Changing to Celsius
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter
USER password 2000.
3. Press UP or DOWN keys to scroll to
Sys Config
;
press ENTER key.
4. Press UP or DOWN keys to scroll to
General
Settings (A1-1)
; press enter key.
5. Press ENTER key to scroll to
UOM
(see Figure 32).
6. Press UP and DOWN keys to change value to
SI
.
FIGURE 32
Changing to Celsius
Configuring Number of Units
The LC is capable of operating up to 14 wall-mount
units in up to 3 zones. This includes MULTI-TEC,
FUSION-TEC WR Series and MEGA-TEC units. Add all
units up for total number of units. Example: If there
are three MULTI-TEC units in Zone 1, two FUSION-TEC
WR units in Zone 2 and one MEGA-TEC unit in Zone 3,
the total number of units should be set to 6.
To configure the total number of units:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
USER password 2000.
3. Press UP or DOWN keys to scroll to
Sys Config
;
press ENTER key.
4. Press UP or DOWN keys to scroll to
General
Settings (A1-1)
; press enter key.
5. Press ENTER key to scroll to
Total Units
(see
Figure 32).
6. Press UP or DOWN keys to adjust value to correct
number of units.
7. Press ENTER key to save value.
User
2000
Technician
1313
Engineer
9254
Use UP or DOWN keys and ENTER key to enter password
TABLE 1
LC6000 Passwords (Defaults)
Message
Description
On
The system is on
Off by Alarm
The system has a major fault and is
disabled
Off by BMS
The system has been disabled by
network supervisor
Off by Keypad
The system has been turned off by
local user
Emergency
Cooling
The system has detected a high
temperature alarm and one or more
zones are emergency cooling
Emergency Vent
The system has detected hydrogen
and one or more zones are in
emergency ventilation
TABLE 2
LC6000 Status Messages