5. Physical installation
2
1
A
B
Image 5-32
5.8
Connecting the hoses with projector and chillers
What has to be done?
The cooling circuit of the chiller(s) has to be connected with the cooling circuit of the projector. For that hoses are needed. The
length of the hoses depend on the position of the chillers in relation to the projector. The maximum length is 10 meter!
The method of connecting the projector with the chillers depends on the type of projector the chiller will be connected to. For proper
connection instructions with your projector, refer to the projector installation manual.
It is also advised to use the correct accessory kit to install the support frames before you connect the hoses
and use the hose shells after connecting the hoses. See the Accessory kit installation manual for more details.
General hoses IN/OUT connection scheme
The labels on the projector and on the chillers indicate the three possible cooling circuits: (
R/B
,
G
and
DMD
) and the direction of the
liquid
fl
ow:
OUT
and
IN
. ’OUT’ means liquid
fl
ows out of the chiller or projector, ’IN’ means liquid
fl
ows into the chiller or projector.
Both sides of all hoses are also labeled.
Chiller without DMD cooling unit
Chiller with DMD cooling unit
Connected projector
DMD OUT
DMD IN
DMD IN
DMD OUT
R/B OUT
R/B IN
G OUT
G IN
G IN
G OUT
R/B IN
R/B OUT
C
AUTION
:
Do not interchange the different cooling circuits with each other! Otherwise the system will fail.
30
R5905866 ULC-30A 31/01/2018
Summary of Contents for ULC-30A
Page 1: ...ULC 30A Installation and user manual R5905866 01 31 01 2018...
Page 4: ......
Page 6: ...Table of contents 2 R5905866 ULC 30A 31 01 2018...
Page 14: ...2 Safety 10 R5905866 ULC 30A 31 01 2018...
Page 36: ...6 Starting up 32 R5905866 ULC 30A 31 01 2018...
Page 44: ...9 Basic replacements 40 R5905866 ULC 30A 31 01 2018...
Page 50: ...11 Environmental information 46 R5905866 ULC 30A 31 01 2018...