IItem
Description
C Insulation plate
Plate of non-combustible material with a thickness of at least 100
mm and a thermal conductivity of at least 0.10 W/m.K
D Air gap
Space between insulation plate and wall. Width of air gap at least 20
mm
E Wall
Existing side and/or rear wall made of combustible material or load-
bearing wall
Caution:
• Put a non-combustible insulating plate with a thickness of at least 40 mm
and a thermal conductivity of not more than 0.10 W/m.K on a distance of at
least 50 mm from a combustible ceiling.
Table 7: Installation against a combustible ceiling
Item
Description
A Appliance
B Ventilation air outlet
Outlet of heated air from the chimney breast
C Insulation plate
Plate of non-combustible material with a thickness of at least 40 mm
and a thermal conductivity of at least 0.10 W/m.K
D Air gap
Space between insulation plate and wall. Width of air gap at least 50
mm
E Ceiling
Existing ceiling made of combustible material
Caution:
• Make sure that brickwork is build with a clearing of at least 3 mm between
the sides and top of the appliance and the brickwork. The appliance can
expand during operation due to heating.
Installation
22
Falcon 59/70
Summary of Contents for Falcon 59/70
Page 1: ...I Installation and maintenance manual Falcon 59 70 Serial number Production date...
Page 27: ...Annual maintenance Falcon 59 70 2 27...
Page 31: ...8 8 Dimensions 8 1 Frameless appliance Dimensions Falcon 59 70 31...
Page 33: ...8 8 3 Appliance with 3 sided classic frame Dimensions Falcon 59 70 33...
Page 34: ...8 8 4 Appliance with 4 sided classic frame Dimensions 34 Falcon 59 70...
Page 37: ...Warranty Terms Falcon 59 70 3 37...
Page 38: ...Warranty Terms 3 38 Falcon 59 70...