17
Operating Instructions
bar-positurn2 and bar-positrol
English
6. Establish power supply.
7. Press the red button for the automa-
tic initialisation longer than 2 seconds.
Chaser light during the initialisation
process
Both end-positions will be reached
two times automatically
8. Initialisation is completed
successfully when all LEDs
illuminate permanently
9. Start up by switching back the
Initialisation switch from
„Init“
to
„Run“.
10. Commissioning is completed.
ATTENTION!
6
7
• Please note that all safety functions are immediately available when switching
the initialisation switch from „Init“ to „Run“. This can cause an immediate
switching of the actuator!
• In case of every (even accidental) switching to „Init“, the whole initialisation
process must be carried out anew, because the previously learned values will
have been lost.
• After every change of the end position and reassembling the actuator, do not
forget to make a new initialisation.