22
English
Operating Instructions
bar-positurn2 and bar-positrol
Description of Safety Functions:
Unit type: PN2-D / PL-D
• Current supply Terminal 13 + 14 missing
• Analog input Terminal 8 missing
• Analog input Terminal 8 < 2 mA
Unit type: PN2-S / PL-S
• Current supply Terminal 13 + 14 missing
• Analog input Terminal 8 missing
• Analog input Terminal 8 < 2 mA
Unit type: PN2-E / PLE
• Current supply Terminal 13 + 14 missing
• Analog input Terminal 8 missing
• Analog input Terminal 8 < 2 mA
Unit type: PN2-D / PL-D
• Current supply Terminal 13 + 14 missing
• Analog input Terminal 8 missing
Unit type: PN2-S / PL-S
• Current supply Terminal 13 + 14 missing
• Analog input Terminal 8 missing
Unit type: PN2-E / PL-E
• Current supply Terminal 13 + 14 missing
• Analog input Terminal 8 missing
Valve persists in last position
Valve persists in last position
Valve persists in last position
Valve moves to safety position
Valve moves to safety position
Valve moves to safety position
Valve moves to safety position
Valve moves to safety position
Valve moves to safety position
Valve persists in last position
Valve moves to 0 Volt-position
Valve moves to safety position
Valve moves to 0 Volt-position
Valve moves to safety position
Valve moves to 0 Volt-position
Positioner mode 4–20 mA:
Positioner mode 0–10 V: