Installation & Operating Instructions

BAPI-Stat 4 Sensor, w/Display, Button Setpoint, Fan or System Mode Control

BA/BS4M  Temperature Sensor

Specifications subject to change without notice.

rev. 01/18/16

25188_ins_BS4M

3 of 8

Optional Test and Balance Switch (S1)

Optional Communication Jack Wiring

Fig. 7: 

Back Plate 

Comm. 

Jack 

Locations

Fig. 8: 

C35L 

Comm. Jack 

(3.5mm plug 

shown for 

clarity)

Fig. 9:

C11/C22

Comm. 

Jack

C35L

C11L/

C22L

PIN #

WIRE COLOR

1

Not Connected

2

Black

3

Red

4

Yellow

5

Green

6

Not Connected

C11L/C22L Comm. Jack Wiring

Location

WIRE COLOR

Ground

Black

Tip

White

Ring

Red

C35L Comm. Jack Wiring

Sensor Type

Low Temp (40° F)

Resistance Value

High Temp (105°F)

Resistance Value

1000Ω RTD

1.02KΩ (41.20°F)

1.15KΩ (101.5°F)

3000Ω Thermistor

7.87KΩ (39.8°F)

1.5KΩ (106.8°F)

10K-2 Thermistor

30.1KΩ (34.9°F)

4.75Ω (109.1°F)

10K-3 Thermistor

26.7KΩ (35.9°F)

5.11KΩ (108.4°F)

10K-3(11K) Thermistor

7.32KΩ (43.7°F)

3.65Ω (105.2°F)

Test and Balance Switch (S1)

NORM: Sensor operates normally

LOW: Sets the sensor value low

HIGH: Sets the sensor value high

On the Test and Balance Switch, the NORM position allows the real sensor to be monitored. The HIGH position forces the 

output to a very hot reading and the LOW position forces a very cold reading (see Table below).

Optional Fan Speed and System Mode Control

Option

Heat/Auto

Off /Auto

Cool/Auto

Heat/On

Off/On

Cool/On

HCF

5KΩ

10KΩ

15KΩ

20KΩ

25KΩ

30KΩ

H01

2KΩ

4KΩ

6KΩ

8KΩ

10KΩ

Option

Heat

Cool

Auto

Off

H02

5KΩ

10KΩ

15KΩ

20KΩ

Option

OFF

AUTO

LO

MED

HI

ON

XLD

5KΩ

10KΩ

15KΩ

20KΩ

25KΩ

X01

4.89KΩ

2.33KΩ

10.63KΩ

13.24KΩ

16.33K

X02

2KΩ

4KΩ

6KΩ

8KΩ

10KΩ

X03

5KΩ

10KΩ

15KΩ

X05

4.89KΩ

2.33KΩ

15.8KΩ

X06

6.5KΩ

8.5KΩ

10.5KΩ

12KΩ

X07

5KΩ

15KΩ

X08

12.68KΩ

11.86KΩ

13.86KΩ

The unit is available with 

optional Fan Speed and 

System Mode Control. 

The resistive outputs for 

the various options is 

shown in the table at right. 

The option is selected at 

the time of order and the 

resistive value is output to 

the FAN terminal.

Summary of Contents for BAPI-Stat 4M

Page 1: ... lock down screws using a 1 16 Allen wrench until they are flush with the bottom of the cover DRYWALL MOUNTING 1 Place the base plate against the wall where you want to mount the sensor 2 Using a pencil mark out the two mounting holes and the area where the wires will come through the wall 3 Drill two 3 16 holes in the center of each marked mounting hole Insert a drywall anchor into each hole 4 Dr...

Page 2: ...der voltage SET1 is SET2 is If the unit is a common ground configuration CG see Grounding Note below OVR1 OVR2 Override output Dry contact The contact can be ordered as a momentary shunt across the sensor N or as a momentary shunt across the setpoint P or as a separate momentary contact J or as a separate latching contact L If the unit is a common ground configuration CG see Grounding Note below R...

Page 3: ...hermistor 7 32KΩ 43 7 F 3 65Ω 105 2 F Test and Balance Switch S1 NORM Sensor operates normally LOW Sets the sensor value low HIGH Sets the sensor value high On the Test and Balance Switch the NORM position allows the real sensor to be monitored The HIGH position forces the output to a very hot reading and the LOW position forces a very cold reading see Table below Optional Fan Speed and System Mod...

Page 4: ...shows a fully featured sensor NUMERICAL DISPLAY The default display shows current temperature When the up down buttons are pushed then the display will show and adjust the current setpoint and hold the display for 3 to 4 seconds The unit can also be set up to display setpoint only or for setpoint lockout See Optional Technicians Adjustments section BAPI MAN ICON The BAPI Man Icon shows the status ...

Page 5: ... Override S5 Up Adjust and S6 Down Adjust See Fig 14 After adjustment place the board back into the cover and insert the center mounting screw Do not over tighten MODE MENUS The setup mode consists of menu pages P1 through P6 for configuring the sensor The following adjustments can be done with the program jumper J16 installed P1 Temperature offset Adjust Up or Down 5 to 5 in 0 1 increments P2 Set...

Page 6: ...d when there is a ground signal to the EXT OVR terminal of the unit For Option 9 the BAPI Man Icon stays filled or solid when the relay is closed and hollow when the relay is open For Option 10 the BAPI Man Icon is disabled but the ON or OFF Dot on the display is controlled by the EXT OVR terminal When there is a ground signal at the EXT OVR terminal the ON dot is lit Otherwise the OFF and hollow ...

Page 7: ...ly Check that the resistance across the override output is less than 5Ω when the override is pushed Fan Mode not correct Make sure that the fan mode output is correct Remove the fan mode output wire and check the output for the correct resistance See the product label for your specific range and compare it to the resistance chart at the bottom of page 3 Don t forget to reconnect the wire When the ...

Page 8: ...uts Dry contact 24V 1mA Occupied EXT OVR Grounded Unoccupied EXT OVR Open to Ground Display LCD Overall 2 W x 1 1 H Temp Setpoint Occupied LCD 3 5 Digits 0 6 H Occ Unocc BAPI Man Icon Filled in man is occupied Display Limits 1 0º 0 5 and 0 1 F C increments Setpoints in 1º steps Range 40 to 185 F 40 to 85 C Display Setup Temp Setpoint Temp only or Setpoint only ºF or ºC Optional Fan Speed System Mo...