background image

5 of 8

Installation & Operating Instructions

BAPI-Stat 4 Sensor, w/Display, Button Setpoint, Fan or System Mode Control

BA/BS4M  Temperature Sensor

rev. 01/18/16

25188_ins_BS4M

Optional Technician Adjustments 

(The sensor set-up is factory set per your order. Set-up adjustments are not required)

The unit is shipped ready to install per the order and does not requires any special setup or programming.  The following 

Setup or Program Menu Changes are available if the installer decides to change the factory settings. Pushing the button 

(S2) on the lower right side of the termination board allows the user to change the display from Celsius to Fahrenheit and 

back again (See Fig. 6).

ENTERING PROGRAM MODE AND MAKING CHANGES:

1.  Remove cover and install the shunt jumper across the J16 pins (see Fig. 13). 
2.  Use the Up and Down Setpoint Pushbuttons on the front of the sensor to advance 

to the parameter you wish to adjust. (Moves up or down from page to page or from 

setting to setting.) 

3.  Push the Override Pushbutton on the front of the unit to select the menu adjust 

parameter. This selects the currently displayed menu. 

4.  Use the Up and Down pushbuttons to adjust the parameter
5.  Push the Override Pushbutton to select the newly adjusted parameter value.
6.  You can quit by removing J16 or move to the next parameter using the Up/Down Setpoint buttons.  
Note:  If your unit does not have the necessary front Up/Down/Override buttons for 

adjustment you can remove the board from the housing and use the three 

buttons that are on the back of the board.  Removing the board requires 

removing the centered board mounting screw.  The buttons are identified as S3 

= Enter (Override), S5 = Up Adjust and S6 = Down Adjust. (See Fig. 14)  After 

adjustment, place the board back into the cover and insert the center mounting 

screw.  Do not over tighten.

MODE MENUS: 

The setup mode consists of menu pages P1 through P6 for configuring the sensor.  

The following adjustments can be done with the program jumper J16 installed.  

P1 = Temperature offset:

 Adjust Up or Down, -5 to 5° in 0.1° increments

P2 = Setpoint Lockout:

 Adjust the value to define the Setpoint mode

    0  = Enable Setpoint adjustment (Normal mode)

    1  = Disable Setpoint adjustment (No setpoint adjust)

    2 = Display Setpoint Only (No room temperature displayed)

    3 = No Setpoint Displayed (Rarely used with pushbutton setpoint units)

P3 = Latching Displa

y (see Fig. 15)

     -1  = Override Disabled

   0   = Momentary Contact, Hollow Man/Solid Man (Typically the normal setting)

    1   = Latching Contact: Off/On, No Fan/Fan, Solid Man 

    2   = Latching Contact: Off/On, No Fan/Fan, No BAPI-Man

    3   = Latching Contact: Off/On, Solid Man

    4   = Latching Contact: Off/On, No BAPI-Man

      5   = Latching Contact: On/Off, Fan/No Fan, Solid Man  

    6   = Latching Contact: On/Off, Fan/No Fan, No BAPI-Man

    7   = Latching Contact: On/Off, Solid Man 

    8   = Latching Contact: On/Off, No BAPI-Man

    9   = Latching Contact: Hollow Man/Solid Man

    10 = Non-Latching
    See “Latching Override Operation” and “Momentary Override Operation” descriptions for further details. 

P4 = Temperature Display: 

Adjust value to the display increments desired

    0  = Display in whole digits only 

    1  = Display in 0.5° increments, F or C as chosen on switch S2

    2  = Display in 0.1° increments, F or C as chosen on switch S2 

 

 

 

P5 = Setpoint Display Low: 

Adjust the Low temperature of the desired setpoint range between -9 to 99°.

P6 = Setpoint Display High:

 Adjust the High temperature of the desired setpoint range between -9 to 99°.

Fig. 13:

 J16 Program 

Jumper

Jumper On 

Program Mode

Jumper Off 

Run Mode

Fig. 14:

 Setup Switch 

locations on the circuit board

 Up

Enter

Down

Summary of Contents for BAPI-Stat 4M

Page 1: ... lock down screws using a 1 16 Allen wrench until they are flush with the bottom of the cover DRYWALL MOUNTING 1 Place the base plate against the wall where you want to mount the sensor 2 Using a pencil mark out the two mounting holes and the area where the wires will come through the wall 3 Drill two 3 16 holes in the center of each marked mounting hole Insert a drywall anchor into each hole 4 Dr...

Page 2: ...der voltage SET1 is SET2 is If the unit is a common ground configuration CG see Grounding Note below OVR1 OVR2 Override output Dry contact The contact can be ordered as a momentary shunt across the sensor N or as a momentary shunt across the setpoint P or as a separate momentary contact J or as a separate latching contact L If the unit is a common ground configuration CG see Grounding Note below R...

Page 3: ...hermistor 7 32KΩ 43 7 F 3 65Ω 105 2 F Test and Balance Switch S1 NORM Sensor operates normally LOW Sets the sensor value low HIGH Sets the sensor value high On the Test and Balance Switch the NORM position allows the real sensor to be monitored The HIGH position forces the output to a very hot reading and the LOW position forces a very cold reading see Table below Optional Fan Speed and System Mod...

Page 4: ...shows a fully featured sensor NUMERICAL DISPLAY The default display shows current temperature When the up down buttons are pushed then the display will show and adjust the current setpoint and hold the display for 3 to 4 seconds The unit can also be set up to display setpoint only or for setpoint lockout See Optional Technicians Adjustments section BAPI MAN ICON The BAPI Man Icon shows the status ...

Page 5: ... Override S5 Up Adjust and S6 Down Adjust See Fig 14 After adjustment place the board back into the cover and insert the center mounting screw Do not over tighten MODE MENUS The setup mode consists of menu pages P1 through P6 for configuring the sensor The following adjustments can be done with the program jumper J16 installed P1 Temperature offset Adjust Up or Down 5 to 5 in 0 1 increments P2 Set...

Page 6: ...d when there is a ground signal to the EXT OVR terminal of the unit For Option 9 the BAPI Man Icon stays filled or solid when the relay is closed and hollow when the relay is open For Option 10 the BAPI Man Icon is disabled but the ON or OFF Dot on the display is controlled by the EXT OVR terminal When there is a ground signal at the EXT OVR terminal the ON dot is lit Otherwise the OFF and hollow ...

Page 7: ...ly Check that the resistance across the override output is less than 5Ω when the override is pushed Fan Mode not correct Make sure that the fan mode output is correct Remove the fan mode output wire and check the output for the correct resistance See the product label for your specific range and compare it to the resistance chart at the bottom of page 3 Don t forget to reconnect the wire When the ...

Page 8: ...uts Dry contact 24V 1mA Occupied EXT OVR Grounded Unoccupied EXT OVR Open to Ground Display LCD Overall 2 W x 1 1 H Temp Setpoint Occupied LCD 3 5 Digits 0 6 H Occ Unocc BAPI Man Icon Filled in man is occupied Display Limits 1 0º 0 5 and 0 1 F C increments Setpoints in 1º steps Range 40 to 185 F 40 to 85 C Display Setup Temp Setpoint Temp only or Setpoint only ºF or ºC Optional Fan Speed System Mo...

Reviews: