background image

Installation & Operating Instructions

BAPI-Stat 4 Sensor, w/Display, Button Setpoint, Fan or System Mode Control

BA/BS4M  Temperature Sensor

Specifications subject to change without notice.

rev. 01/18/16

25188_ins_BS4M

7 of 8

General Diagnostics

POSSIBLE PROBLEM: 

POSSIBLE SOLUTIONS:

Temperature reading is incorrect 

- Verify that the input is set up correctly in the controller’s and building 

automation software.

 

- Check wiring for proper termination and check for opens or shorts.

 

- Measure the room temperature at the sensor’s location using an accurate 

temperature standard.  Disconnect the temperature sensor wires and 

measure the temperature sensor’s resistance across the sensor output 

pins with an ohmmeter.  Compare the temperature sensor’s resistance 

to the appropriate temperature sensor table on the BAPI website.  If the 

measured resistance varies by more than 5% from the temperature table, 

call BAPI technical support.  To view the temperature table, go to the BAPI 

website (www.bapihvac.com), click on “Resource Library” and “Sensor 

Specs”, then click on the type of sensor you have.

 

- If the unit has a test and balance switch, make sure that it is in the correct 

position.

Setpoint reading is incorrect 

- Make sure that the setpoint output is correct.  Remove the setpoint output 

wire and check the output for the correct resistance or voltage output.  See 

the product label for your specific range. 

Override is not working correctly 

- Check that the resistance across the override output is less than 5Ω when 

the override is pushed.

Fan Mode not correct 

- Make sure that the fan mode output is correct.  Remove the fan mode 

output wire and check the output for the correct resistance.  See the 

product label for your specific range and compare it to the resistance chart 

at the bottom of page 3. Don’t forget to reconnect the wire.

When the Override pushbutton is pressed, the BAPI-Man (Fig. 11) will be displayed as “Solid” for 3-5 seconds and the 

override output will shunt or short for 3 seconds depending on the override option selected. The various options are 

described below. 
  -N Option = Momentary Temperature Sensor Shunt to < 15Ω 

  -P Option = Momentary Setpoint Shunt to <15Ω 

  -J Option = Momentary Override as a Separate Shorting Contact Output on OVR1 & OVR2

BAPI-MAN ICON:

 

The BAPI-Man Icon shows the status of the room – Solid for Occupied, Hollow for “Unoccupied” (Fig. 11). The unit must 

receive a confirmation (ground) signal on the “EXT OVR” terminal for the BAPI-Man to remain visible on the screen. 

Pressing the Override button will light the BAPI-Man icon; however, if no confirmation signal is received, then the BAPI-

Man will go blank (disappear) after 5 seconds.  Upon receiving a first confirmation (ground) signal on the “EXT OVR” 

terminal, the BAPI-Man will show occupied (Solid). The BAPI-Man will then show unoccupied (Hollow) whenever the 

confirmation signal is removed and occupied when the signal is returned. The only way to blank or remove the BAPI-Man 

from the display after receiving a confirmation signal is to cycle power.

 Momentary Override Operation (Non-Latching)

Summary of Contents for BAPI-Stat 4M

Page 1: ... lock down screws using a 1 16 Allen wrench until they are flush with the bottom of the cover DRYWALL MOUNTING 1 Place the base plate against the wall where you want to mount the sensor 2 Using a pencil mark out the two mounting holes and the area where the wires will come through the wall 3 Drill two 3 16 holes in the center of each marked mounting hole Insert a drywall anchor into each hole 4 Dr...

Page 2: ...der voltage SET1 is SET2 is If the unit is a common ground configuration CG see Grounding Note below OVR1 OVR2 Override output Dry contact The contact can be ordered as a momentary shunt across the sensor N or as a momentary shunt across the setpoint P or as a separate momentary contact J or as a separate latching contact L If the unit is a common ground configuration CG see Grounding Note below R...

Page 3: ...hermistor 7 32KΩ 43 7 F 3 65Ω 105 2 F Test and Balance Switch S1 NORM Sensor operates normally LOW Sets the sensor value low HIGH Sets the sensor value high On the Test and Balance Switch the NORM position allows the real sensor to be monitored The HIGH position forces the output to a very hot reading and the LOW position forces a very cold reading see Table below Optional Fan Speed and System Mod...

Page 4: ...shows a fully featured sensor NUMERICAL DISPLAY The default display shows current temperature When the up down buttons are pushed then the display will show and adjust the current setpoint and hold the display for 3 to 4 seconds The unit can also be set up to display setpoint only or for setpoint lockout See Optional Technicians Adjustments section BAPI MAN ICON The BAPI Man Icon shows the status ...

Page 5: ... Override S5 Up Adjust and S6 Down Adjust See Fig 14 After adjustment place the board back into the cover and insert the center mounting screw Do not over tighten MODE MENUS The setup mode consists of menu pages P1 through P6 for configuring the sensor The following adjustments can be done with the program jumper J16 installed P1 Temperature offset Adjust Up or Down 5 to 5 in 0 1 increments P2 Set...

Page 6: ...d when there is a ground signal to the EXT OVR terminal of the unit For Option 9 the BAPI Man Icon stays filled or solid when the relay is closed and hollow when the relay is open For Option 10 the BAPI Man Icon is disabled but the ON or OFF Dot on the display is controlled by the EXT OVR terminal When there is a ground signal at the EXT OVR terminal the ON dot is lit Otherwise the OFF and hollow ...

Page 7: ...ly Check that the resistance across the override output is less than 5Ω when the override is pushed Fan Mode not correct Make sure that the fan mode output is correct Remove the fan mode output wire and check the output for the correct resistance See the product label for your specific range and compare it to the resistance chart at the bottom of page 3 Don t forget to reconnect the wire When the ...

Page 8: ...uts Dry contact 24V 1mA Occupied EXT OVR Grounded Unoccupied EXT OVR Open to Ground Display LCD Overall 2 W x 1 1 H Temp Setpoint Occupied LCD 3 5 Digits 0 6 H Occ Unocc BAPI Man Icon Filled in man is occupied Display Limits 1 0º 0 5 and 0 1 F C increments Setpoints in 1º steps Range 40 to 185 F 40 to 85 C Display Setup Temp Setpoint Temp only or Setpoint only ºF or ºC Optional Fan Speed System Mo...

Reviews: