Installation & Operating Instructions

BAPI-Stat 4 Sensor, w/Display, Button Setpoint, Fan or System Mode Control

BA/BS4M  Temperature Sensor

Specifications subject to change without notice.

rev. 01/18/16

25188_ins_BS4M

8 of 8

Specifications

Power for 5 VDC Power Units:

  0 to 5 VDC Setpoint or Resistive Setpoint ....5V ±1% (5 VDC nominal, Input regulation affects accuracy)

Power for 24 VDC Power Units:

  0 to 5 VDC Setpoint or Resistive Setpoint  ...9 to 40 VDC (24 VDC nominal)

  0 to 10 VDC Setpoint or Resistive Setpoint ..15 to 40 VDC (24 VDC nominal)

  Any Allowed Setpoint ....................................15 to 28 VAC (24 VAC nomimal)

   Note: AC power requires a separate pair of shielded wires

Power Consumption:

 .....................................7 mA max DC; .17 VA maximum AC

Wiring:

 ...................See Wiring & Termination Section, 22 to 14AWG

Mounting:

 ..............Standard 2 x 4” box or drywall direct, Screws provided

Outputs:

   Passive Sensor....See order grid for thermistor or RTD 

   

Thermistor, ±0.36ºF (±0.2ºC), [XP] ±0.18ºF (±0.1ºC)

   

Platinum RTD, ±0.12%, [A] ±0.06%

   

Nickel RTD, 1000Ω @70ºF, JCI curve 

  External Sensor ...10K-2 thermistor (-ES), (Purchased separately) Wired 25’ maximum from sensor

  Setpoint ...............Resistive per order or voltage (0 to 10VDC limit per order)

  Isolated Contact ..24VDC @500mA resistive

Inputs:

 ....................Dry contact (24V, <1mA)

 

Occupied .............EXT OVR “Grounded”

  Unoccupied .........EXT OVR “Open to Ground”

Display: 

.................LCD, Overall, 2”W x 1.1”H (Temp/Setpoint/Occupied)

  LCD  ....................3.5 Digits @0.6”H 

  Occ/Unocc  ..........BAPI-Man Icon, (Filled in man is occupied) 

  Display Limits ......1.0º, 0.5° and 0.1° (F/C) increments, Setpoints in 1º steps

  Range  .................-40 to 185°F (-40 to 85°C)

  Display Setup ......Temp. & Setpoint, Temp. only, or Setpoint only, ºF or ºC

  Optional ...............Fan Speed, System Mode, Override 

Button Options:

 ....Factory set options

  Setpoint  ..............Up & Down buttons

  Override ..............Pushbutton

  Override ..............Factory set to Momentary shunt across sensor, Momentary shunt across setpoint, 

   

Momentary isolated contact or Latching isolated contact

  Fan Speed ...........Off, Auto, Lo, Med, Hi

  System Mode ......Heat/Off/Cool, Auto/On Fan

Setup Options:

  Offset ...................±5º

   Temp Display .......Display in ºF or ºC

   Setpoint ...............Disabled or Setpoint display only

  Resolution ...........Display in 1.0°, 0.5º or 0.1º increments

Other Options:

   Comm. jack .........3.5mm phone jack, 3 wires (-C35) • RJ11 jack, 4 wires (-C11) • RJ22 jack, 4 wires (-C22)

  Test & Balance ....Three position switch (-TB), (High Temp/Normal/Low Temp)

  Common Ground .Internal common connection (-CG)

  Differential GND. .Each output terminal is isolated (-DF)

Environmental Ambient: 

  Temperature ........32 to 122ºF (0 to 50ºC)

  Humidity ..............0 to 95% RH Non-condensing

  Storage ................32 to 185°F (0 to 85°C)

Encl. Material:

 .......ABS Plastic, UL94V-0

Agency:

 .................RoHS, CE* (*Units with passive Thermistors 20KΩ and smaller are CE compliant.)

Summary of Contents for BAPI-Stat 4M

Page 1: ... lock down screws using a 1 16 Allen wrench until they are flush with the bottom of the cover DRYWALL MOUNTING 1 Place the base plate against the wall where you want to mount the sensor 2 Using a pencil mark out the two mounting holes and the area where the wires will come through the wall 3 Drill two 3 16 holes in the center of each marked mounting hole Insert a drywall anchor into each hole 4 Dr...

Page 2: ...der voltage SET1 is SET2 is If the unit is a common ground configuration CG see Grounding Note below OVR1 OVR2 Override output Dry contact The contact can be ordered as a momentary shunt across the sensor N or as a momentary shunt across the setpoint P or as a separate momentary contact J or as a separate latching contact L If the unit is a common ground configuration CG see Grounding Note below R...

Page 3: ...hermistor 7 32KΩ 43 7 F 3 65Ω 105 2 F Test and Balance Switch S1 NORM Sensor operates normally LOW Sets the sensor value low HIGH Sets the sensor value high On the Test and Balance Switch the NORM position allows the real sensor to be monitored The HIGH position forces the output to a very hot reading and the LOW position forces a very cold reading see Table below Optional Fan Speed and System Mod...

Page 4: ...shows a fully featured sensor NUMERICAL DISPLAY The default display shows current temperature When the up down buttons are pushed then the display will show and adjust the current setpoint and hold the display for 3 to 4 seconds The unit can also be set up to display setpoint only or for setpoint lockout See Optional Technicians Adjustments section BAPI MAN ICON The BAPI Man Icon shows the status ...

Page 5: ... Override S5 Up Adjust and S6 Down Adjust See Fig 14 After adjustment place the board back into the cover and insert the center mounting screw Do not over tighten MODE MENUS The setup mode consists of menu pages P1 through P6 for configuring the sensor The following adjustments can be done with the program jumper J16 installed P1 Temperature offset Adjust Up or Down 5 to 5 in 0 1 increments P2 Set...

Page 6: ...d when there is a ground signal to the EXT OVR terminal of the unit For Option 9 the BAPI Man Icon stays filled or solid when the relay is closed and hollow when the relay is open For Option 10 the BAPI Man Icon is disabled but the ON or OFF Dot on the display is controlled by the EXT OVR terminal When there is a ground signal at the EXT OVR terminal the ON dot is lit Otherwise the OFF and hollow ...

Page 7: ...ly Check that the resistance across the override output is less than 5Ω when the override is pushed Fan Mode not correct Make sure that the fan mode output is correct Remove the fan mode output wire and check the output for the correct resistance See the product label for your specific range and compare it to the resistance chart at the bottom of page 3 Don t forget to reconnect the wire When the ...

Page 8: ...uts Dry contact 24V 1mA Occupied EXT OVR Grounded Unoccupied EXT OVR Open to Ground Display LCD Overall 2 W x 1 1 H Temp Setpoint Occupied LCD 3 5 Digits 0 6 H Occ Unocc BAPI Man Icon Filled in man is occupied Display Limits 1 0º 0 5 and 0 1 F C increments Setpoints in 1º steps Range 40 to 185 F 40 to 85 C Display Setup Temp Setpoint Temp only or Setpoint only ºF or ºC Optional Fan Speed System Mo...