EIP Assembly Instance 112
DXM Local Registers
Adrs
Data
Adrs
Data
00
11
01
11 22
01
22
02
33
05
33 44
03
44
04
55
10
55 66
05
66
The following table shows DXM local registers 10, 11, and 19 defined as EIP DXM -> Originator. The lower 2-bytes of each
register data is placed into assembly instance 100.
EIP Assembly Instance 112
DXM Local Registers
Adrs
Data
Adrs
Data
00
77
10
77 88
01
88
02
99
11
99 10
03
10
04
11
19
11 12
05
12
8.5 Setting up Email and Text Messaging
The DXM can be configured to send email or SMS messages based on threshold conditions.
Important: Only the DXM100 and DXM150 models offer SMS/text messaging capabilities.
Cellular-connected systems can use email or SMS. Ethernet-connected systems can only use email, but can send email to
cellular phones as a SMS message depending upon the network carrier. To send email to a Verizon phone, use the phone
number followed by
@vtext.com
, for example, [email protected].
For more information, refer to the DXM Configuration Software Instruction Manual (p/n
). Internal log files may be
sent using email. Follow these instructions and use the DXM Configuration Software to program the controller for email
and/or SMS.
1. On the Settings > System screen, set the Device Time on the DXM1200.
2. On the Settings > Cloud Services screen, select either Ethernet or Cell for the Push Interface.
3. If you selected Ethernet, configure your Ethernet connection by setting the IP settings on the Ethernet screen. If you
selected a Push interface of Cell, use the Cellular screen to define parameters.
4. Set the email and message parameters on the Notifications screen.
5. To send alert messages, define the threshold rule to use email and/or SMS.
6. To send log files, define the log file parameters.
8.5.1 Mail Server Authentication
Complete the mail server settings to have the DXM1200 send email alert messages or to email the log files.
The SMTP password is stored in the DXM1200, not the XML configuration file. Use the Settings > Notifications screen to
complete this configuration.
Sure Cross
®
DXM1200-Bx Wireless Controller
48
www.bannerengineering.com - Tel: + 1 888 373 6767