background image

Figure 1. LED unit internal circuit

X1

X2

LED

R

Figure 2. Applicable Crimping Terminal

ø3.2 min.

ø6.0 max.

4.7 min.

3.0 max.

6.0 max.

3.2 max.

4.7 to 5.9

Insulation Tube

Crimping
Terminal

Ring Terminal

Spade Terminal

Solid Wire

Wire

4.7 to 5.9

4.7 to 5.9

6.2 max.

Insulation Tube

Crimping
Terminal

Wire

ø1.2 max.

Banner recommends the use of crimp terminals with stranded wire or solid core wire to prevent short circuits between terminals.

Ensure that the insulation tube is installed on crimp terminals.

Installing and Removing the Terminal Cover

Install the SSA-EB1-TC Terminal Cover

1. Align the TOP mark on the SSA-EB1-TC terminal cover with the TOP mark on the contact block.
2. Place the two projections on the bottom of the contact block into the slots in the SSA-EB1-TC terminal cover.

Place projections

on contact block

Press on the

terminal cover

TOP Mark

Slots

3. Press the SSA-EB1-TC terminal cover toward the contact block.

Remove the SSA-EB1-TC Terminal Cover

1. Pull out the two latches on the top of the SSA-EB1-TC terminal cover. Do not exert excessive force on the latches, or the

latches may break.

Projections

(pull)

2. Remove the SSA-EB1-TC terminal cover.

SSA-EB Series Emergency Stop Push Button

 

 

P/N 194992 Rev. D

www.bannerengineering.com - Tel: + 1 888 373 6767

5

Summary of Contents for SSA-EB Series

Page 1: ...quirements of the isolation of hazardous energy see OSHA 29CFR1910 147 ANSI Z244 1 CSA Z460 ISO 14118 The locking feature can be used to provide supervisory personal control and provide an additional...

Page 2: ...es WARNING Connect two or more devices to the same safety module controller in series Connecting devices in parallel defeats the switch contact monitoring ability of the module and creates an unsafe c...

Page 3: ...hten the M30 jam nut using wrench SSA EB1 LRW or SSA EB1 LRTW to a maximum torque of 2 5 N m 1 8 ft lbs Note The allowable panel thickness is 1 mm to 5 mm for SSA EB1P and 1 mm to 6 mm for SSA EB1M Ba...

Page 4: ...PL1 11 SSA EB1ML1P 11 1 normally closed NC 1 normally open NO 11 12 X2 23 24 X1 LED24V SSA EB1P 13 SSA EB1MP 13 3 normally closed NC 1 normally open NO 22 11 12 21 41 42 34 33 SSA EB1PL1 13 SSA EB1ML1...

Page 5: ...Cover Install the SSA EB1 TC Terminal Cover 1 Align the TOP mark on the SSA EB1 TC terminal cover with the TOP mark on the contact block 2 Place the two projections on the bottom of the contact block...

Page 6: ...hould test each safety point for proper machine shutdown response A Designated Person should check the safety point for proper operation physical damage button looseness and excessive environmental co...

Page 7: ...mA Output Configuration See Installation and Maintenance on page 2 Mechanical Life 250 000 operations Terminals M3 screw terminal terminal cover included Recommended Torque 0 6 to 1 0 N m 5 3 to 8 8 i...

Page 8: ...0947 5 1 See Electrical Rating above for specific model and UL CE maximum ratings Required Overcurrent Protection WARNING Electrical connections must be made by qualified personnel in accordance with...

Page 9: ...rol units of different sizes and styles determine the values according to the dimensions operation and wiring convenience For padlock style lockable emergency stop push buttons determine the values ac...

Page 10: ...d contact blocks including LED indicators are only available as complete units and are not sold separately SSA EB1 FSTC IP20 Finger safe terminal cover SSA EB1 TC Standard terminal cover supplied SSA...

Page 11: ...Assessment and Risk Reduction ISO 13850 EN 418 Emergency Stop Devices Functional Aspects Principles for Design IEC 62061 Functional Safety of Safety Related Electrical Electronic and Programmable Cont...

Page 12: ...RA COSTS EXPENSES LOSSES LOSS OF PROFITS OR ANY INCIDENTAL CONSEQUENTIAL OR SPECIAL DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE THE PRODUCT WHETHER ARISING IN CONTRAC...

Reviews: