1.
Press
to enter the TEACH-IN menu.
The sensor displays the selected output. TEACH-IN > <SETQ1>.
2.
Press
or
to scroll through the output
options:
<SETQ1>, <SETQ2>, or <ANALOG> (only for
diffuse
models).
3.
Press
to select an output.
The sensor displays the current output and mode
selections.
4.
Press
or
to scroll through Output 1
options:
Mode Q1, TEACH 1.1, TEACH 1.2, HYST 1.
The sensor displays the TEACH
options
for the selected output.
5.
Press
to view the output mode
options.
The sensor displays an arrow to indicate that the
options
can be viewed.
6.
Press
or
to scroll through the output mode
options.
7.
Press
to select an output mode
option.
The sensor saves the selected output mode
option.
8.
Press
or
to scroll through Output 1
options:
TEACH 1.1, <203>.
The sensor again displays TEACH
options
for the selected output.
9.
Press
to select an
option:
TEACH 1.1, 203.
The sensor is ready to learn Limit 1.
10.
Press
to teach the target
condition.
The sensor saves the Limit 1
setting
and returns to the Output 1 menu level.
11.
Press
to access Manual Adjust.
12.
Press
to decrease or
to increase the value of each digit.
The
flashing
cursor indicates the digit is
active,
starting
with the fourth digit
location
from the
left.
13.
Press
to select the digit and move it to the
left
by one digit
location.
14.
Press
when the cursor
flashes
on the
first
digit on the
left
and the value is correct.
The sensor saves the
setting
and returns to the Output 1 menu level.
15.
Press
to teach the Limit 1.2 from the Output 1 menu. TEACH 1.2 > <12000>.
The sensor again displays the TEACH
options
for the selected output. Repeat the procedure for Limit 1.1.
16.
Press
to select the Hysteresis
function.
HYST 1 > <±005> .
The
flashing
cursor indicates that the digit is
active,
starting
with the fourth digit
location
from the
left.
The minimum factory default
setting
for hysteresis is ± 005. The maximum
setting
for hysteresis is ± 254 mm (± 9.99 in).
17.
Press
to decrease and
to increase the value of each digit.
18.
Press
to select the digit and move it to the
left
by one digit
location.
19.
Press
when the cursor is on the
first
digit on the
left
and the value is correct.
• HYST 1 > <±254> if the value is valid.
• HYST 1 > Limited! if the value is outside accepted limits.
The sensor saves the
setting
and returns to the HYST 1 menu level.
20.
Press
or
to return to other Output 1
functions
or press Escape to move up one menu level.
The TEACH procedure for Output 1 and Output 2 is the same. If the value is outside accepted limits, the sensor does not save the new
setting.
L-GAGE
®
LT7 Long-Range Time-of-Flight Laser Sensor
10
www.bannerengineering.com - Tel: +1-763-544-3164
P/N 120244 Rev. C