Timeout controls how long the controller waits before determining a command has failed to send. Set the
Timeout based on the specific application requirements. The minimum Timeout interval for Radio (Port 5) is
62.5 ms.
Delay between messages defines the minimum wait time before sending another command. Set the delay
based on the specific application requirements.
RTU Configuration screen
Go to the RTU configuration panel for Radio (Port 5).
b.
Modify the port settings as needed.
c.
From the Register Mapping
›
RTU
›
RTU Read screen, click Add Read Rule.
2.
Click the arrow next to the name to display the parameters.
3.
Name your rule.
4.
Select the port number to which the device is connected. For wireless devices, this is Radio (Port 5).
5.
Select the Modbus ID of the device. For wireless devices, this is
Modbus ID 1.
6.
Select how many registers to read and select the beginning register.
Refer to the Modbus Holding Register table within the documentation for each server device.
7.
Define the register type, how often to read the register, and any other appropriate parameters.
8.
If necessary, select the error condition. For this example, if the read function fails after three attempts, the read rule
writes 12345 to the DXM local registers. Notice the list of local register names this read rule is using.
9.
Summary of Contents for DXM1200-X2